HomeMy WebLinkAboutORDINANCE 6159113 West Mountain Street
Fayetteville, AR 72701
(479) 575-8323
Ordinance: 6159
File Number: 2019-0117
AUTOMATIC ENGINEERING:
AN ORDINANCE TO WAIVE COMPETITIVE BIDDING AND TO ACCEPT A REPAIR QUOTE OF
$140,452.33, PLUS APPLICABLE TAXES, FROM AUTOMATIC ENGINEERING TO REPAIR FOUR
AGITATOR GEARBOXES FOR THE PAUL R. NOLAND WASTEWATER TREATMENT FACILITY
WHEREAS, formal sealed bidding is not necessary for the repair of "hidden or unknown damages";
and
WHEREAS, Automatic Engineering has taken apart and examined four agitator gearboxes and determined
that repair of these gearboxes would cost $140,452.33 plus applicable taxes.
NOW, THEREFORE, BE IT ORDAINED BY THE CITY COUNCIL OF THE CITY OF
FAYETTEVILLE, ARKANSAS:
Section 1. That the City Council of the City of Fayetteville, Arkansas hereby determines that, because of
Ark. Code Ann. §19-11-203(14)(EE), the repair of "hidden or unknown damages" does not require
formal competitive bidding and therefore, waives competitive bidding and accepts Automatic Engineering's
repair quote of $140,452.33 (plus any applicable taxes) and authorizes the payment of that amount.
PASSED and APPROVED on 3/5/2019
Page 1
Attest:
Sondra E. Smith, City Clerk
,N�<<<ti�ttrr►►►►�►
K
f r .•may :�' �■1 T Y 0 10''�.
�.. � •■mss
Printed on 317 1! i t f ►1,►,
City of Fayetteville, Arkansas 113 West Mountain Street
y = Fayetteville, AR 72701
(479) 575-8323
Text File
File Number: 2019-0117
Agenda Date: 3/5/2019 Version: 1 Status: Passed
In Control: City Council Meeting File Type: Ordinance
Agenda Number: C. 8
AUTOMATIC ENGINEERING:
AN ORDINANCE TO WAIVE COMPETITIVE BIDDING AND TO ACCEPT A REPAIR QUOTE OF
$140,452.33, PLUS APPLICABLE TAXES, FROM AUTOMATIC ENGINEERING TO REPAIR FOUR
AGITATOR GEARBOXES FOR THE PAUL R. NOLAND WASTEWATER TREATMENT FACILITY
WHEREAS, formal sealed bidding is not necessary for the repair of "hidden or unknown damages"; and
WHEREAS, Automatic Engineering has taken apart and examined four agitator gearboxes and determined
that repair of these gearboxes would cost $140,452.33 plus applicable taxes.
NOW, THEREFORE, BE IT ORDAINED BY THE CITY COUNCIL OF THE CITY OF
FAYETTEVILLE, ARKANSAS:
Section 1. That the City Council of the City of Fayetteville, Arkansas hereby determines that, because of Ark.
Code Ann. §19-11-203(14)(EE), the repair of "hidden or unknown damages" does not require formal
competitive bidding and therefore, waives competitive bidding and accepts Automatic Engineering's repair
quote of $140,452.33 (plus any applicable taxes) and authorizes the payment of that amount.
City of Fayetteville, Arkansas Page 1 Printed on 3/6/2019
Tim Nyander
Submitted By
City of Fayetteville Staff Review Form
2019-0117
Legistar File ID
3/5/2019
City Council Meeting Date - Agenda Item Only
N/A for Non -Agenda Item
2/13/2019 WASTEWATER TREATMENT (730)
Submitted Date Division / Department
Action Recommendation:
Staff recommends repair of one (1) large and three (3) medium Lightnin brand agitator gearboxes for the Paul R.
Noland Treatment Facility by Automatic Engineering in the amount of $140,452.33 plus estimated applicable taxes
of $13,694.11 for a total of $154,146.44.
5400.730.5800-5414.00
Account Number
02069.1
Budget Impact:
Water and Sewer
Fund
Plant, Pumps and Equipment - WWTP
Project Number
Budgeted Item? Yes Current Budget
Funds Obligated
Current Balance
Does item have a cost? Yes Item Cost
Budget Adjustment Attached? No Budget Adjustment
Purchase Order Number:
Change Order Number:
Original Contract Number:
Comments:
Remaining Budget
Project Title
$
785,080.00
$
202,635.39
V $
582,444.61
_
$
154,146.44
$
428,298.17
Previous Ordinance or Resolution #
Approval Date:
V20180321
CITY OF
FAYETTEVILLE
ARKANSAS
MEETING OF MARCH 5, 2019
TO: Mayor and City Council
THRU: Don Marr, Chief of Staff
Water & Sewer Committee
Tim Nyander, Utilities Director
FROM: Greg Weeks, Wastewater Treatment
DATE: February 13, 2019
CITY COUNCIL MEMO
SUBJECT: Approval of the repair of one (1) large and three (3) medium Lightnin brand
agitator gearboxes for the Noland Treatment Facility
RECOMMENDATION:
Staff recommends repair of one (1) large and three (3) medium Lightnin brand agitator
gearboxes for the Paul R. Noland Treatment Facility by Automatic Engineering in the amount of
$140,452.33 plus applicable taxes.
BACKGROUND:
The Noland Treatment Facility utilizes a series of eight agitator mixers per the EAST and WEST
basin -trains for supplying dissolved oxygen to the biological nutrient removal reactors. The eight
units operate in series using a combination of four large (100 hp) and four medium (50 hp)
Lightnin brand agitator mixers. In recent years these 30+yr old mixers have required over -haul
rebuild corrective maintenance.
DISCUSSION:
Recently, one (1) large and three (3) medium agitator mixers were pulled for disassembly,
inspection and repair proposals. The gearbox units were shipped to Automatic Engineering for
the disassembly and repair inspections. Automatic Engineering has been used to perform
previous gearbox rebuilds in recent years. Return freight for the repaired units is included in the
repair estimates. Staff recommends completion of the repairs of the four gearboxes in the
amount of $140,452.33 plus applicable taxes.
Because it was necessary to have the repair facility disassemble the units to determine the
extent of hidden and unknown damage to equipment already purchased, a bid waiver and/or
formal sealed bidding is not necessary according to Arkansas Procurement Law R6:19-11-
203, Subsection 14 (EE) "hidden or unknown damages"
Mailing Address:
113 W. Mountain Street www.fayetteville-ar.gov
Fayetteville, AR 72701
BUDGET/STAFF IMPACT:
Funds are available within the Wastewater Treatment - Plant Pumps and Equipment project.
Attachments:
Quotes from Automatic Engineering
INSPECTION & ESTIMATE
7013631 -SOD Inspection
1%!:& COGENT
Automatic Engineering
Service Center
'Service Order #
7013631
Date
1/3/2018
'SUID #
Q-36426
:Salesman
Keith Lvett
Customer
City of Fayetteville
Customer Stock #
Contact Name, First
Brian
Service Type
Service
Contact Name, Last
Daniels
Brand
Automatic Engineering
'Contact Phone
479-575-8386
Market
Municipal
Contact Cell
Fluid Being Pumped
N/A Gearbox
Contact Email
Equipment Location/Station
13
Manufacturer
Lightnin
Model
LAT -130
Serial #
8625435603
Item Type / Description
Mixer Gear Box
Additional Items
Coupling Hub, Auto Lubricater, Piping
Level of Repair
L2 - Full DCI with Clearances Noted, Sandblasting, Estimate with Pictures, and Repair Report
DCI Technician JKC
DCI Date
Pump As Found/Received
I Notes:
Gearbox as received for DCI. Lower front & rear
cover panels were missing when gearbox was
received. Since all 4 gearboxes were missing the
panels, we are assuming that the panels are with
the customer, and were not quoted for
replacement.
L -i
INSPECTION & ESTIMATE Page 1 of 7 ANSI Inspection Form V2.5 - Effective 10/2018
INSPECTION & ESTIMATE
7013631 -SOD Inspection
INSPECTION & ESTIMATE Page 2 of 7 ANSI Inspection Form V2.5 - Effective 10/2018
Input Shaft (Bevel Gear)
Inspection Notes
Input Assembly
Teeth are chipped and not repairable.
Inspection Notes
Input shaft bevel gear is chipped, causing the
Aff
Replace input shaft.
assembly rotate rough.
T
f7
!s
Work Scope
L
Replace bearings, shims, and other wear parts.
r.
INSPECTION & ESTIMATE Page 2 of 7 ANSI Inspection Form V2.5 - Effective 10/2018
Input Shaft (Bevel Gear)
Inspection Notes
Teeth are chipped and not repairable.
-
Work Scope
Aff
Replace input shaft.
INSPECTION & ESTIMATE Page 2 of 7 ANSI Inspection Form V2.5 - Effective 10/2018
INSPECTION & ESTIMATE
7013631 -SOD Inspection
INSPECTION & ESTIMATE Page 3 of 7 ANSI Inspection Form V2.5 - Effective 10/2018
Upper Bearing
Inspection Notes
r
Bearing showed normal wear.
� r
tolerance.
_
•
}
Work Scope
Work Scope
Replace with new bearing.
Cleanup, degrease, and reuse.
INSPECTION & ESTIMATE Page 3 of 7 ANSI Inspection Form V2.5 - Effective 10/2018
Upper Bearing Housing
Inspection Notes
Housing in good condition, bearing fit was within
T
tolerance.
_
Work Scope
Cleanup, degrease, and reuse.
INSPECTION & ESTIMATE Page 3 of 7 ANSI Inspection Form V2.5 - Effective 10/2018
INSPECTION & ESTIMATE
7013631 -SOD Inspection
INSPECTION & ESTIMATE Page 4 of 7 ANSI Inspection Form V2.5 - Effective 10/2018
Shaft Coupling
Inspection Notes
-- --
-'.I'r
Shaft hubs and element in good condition.
Work Scope
Clean, degrease, & reuse.
INSPECTION & ESTIMATE Page 4 of 7 ANSI Inspection Form V2.5 - Effective 10/2018
Low Speed Shaft
Inspection Notes
Groove cut into shaft at lip seal fit.
Work Scope
Repair groove in shaft, clean & reuse shaft.
INSPECTION & ESTIMATE Page 4 of 7 ANSI Inspection Form V2.5 - Effective 10/2018
INSPECTION & ESTIMATE
7013631 -SOD Inspection
INSPECTION & ESTIMATE Page 5 of 7 ANSI Inspection Form V2.5 - Effective 10/2018
Intermediary Gearing
Inspection Notes
Gearing in good condition.
Bearings are showing wear, but have not failed.
♦�_
Bearing fits are within tolerance.
4,—
tN
k7
"r
Work Scope
Clean, degrease, and rebuild.
i d
Work Scope
INSPECTION & ESTIMATE Page 5 of 7 ANSI Inspection Form V2.5 - Effective 10/2018
Intermediate Bearings
Inspection Notes e
Bearings are showing wear, but have not failed.
Bearing fits are within tolerance.
"r
i7
Work Scope
Clean and degrease shafts and housings. Replace
bearings, shims, and bearing locknuts/lock
washers.
INSPECTION & ESTIMATE Page 5 of 7 ANSI Inspection Form V2.5 - Effective 10/2018
INSPECTION & ESTIMATE
7013631 -SOD Inspection
INSPECTION & ESTIMATE Page 6 of 7 ANSI Inspection Form V2.5 - Effective 10/2018
how Speed Shaft Bearing Housing
Inspection Notes
{
Bearing fits are within tolerance.
, ,. ,Q.- *~
found.
_
_F Y
Work Scope
i ..1.
Clean and degrease housing. Rebuild with new
shims, oil seals, and retaining rings.
r -�
Clean and degrease housing. Rebuild with new
wear parts and gaskets.
INSPECTION & ESTIMATE Page 6 of 7 ANSI Inspection Form V2.5 - Effective 10/2018
Main Housing
Inspection Notes
{
Housing is in good condition. No stripped holes
-
found.
_
_F Y
i ..1.
Work Scope
r -�
Clean and degrease housing. Rebuild with new
wear parts and gaskets.
„r!
INSPECTION & ESTIMATE Page 6 of 7 ANSI Inspection Form V2.5 - Effective 10/2018
INSPECTION & ESTIMATE 7013631 -SOD Inspection
Conclusions
Paint Tyke and Color I Vista grc-=n I Bin Location I storage container outsidL
Cause of Failure
Normal wear from extended use of the gearbox. Damage to was limited to damage input shaft and groove in low speed shaft. Gearbox will be rebuilt with
new wear parts, including bearings, bearing locknuts/lock washers, oil seals, shims, retaining rings, and gaskets (complete parts list below). The oil level
sensor and oil temperature sensor will be replaced with new units, matching the units installed on previous gearbox repairs. After assembly, the gearboxes
will be painted and shipped back to the customer.
Additional motes & Suggestions
Input shaft need replace( Bevel Gear & pinion) Yellow color code
Parts Required
Packing Ring
Gasket
Seal Ring
Gasket - Cover Plate
Retaining Ring
Bearing
Tapered Adapter Sleeve - Split
Adapter Sleeve - Solid
Locknut & Lockwasher
Oil Seal
Bearing
Gasket
Oil Seal
Locknut
Washer
Bearing
Nose Bearing
Hex Head Capscrew
Hex Head Capscrew
Bevel Pinion
Bearing
Bearing
Bearing
Gasket
Gasket
Oil Seal
Oil Seal
Oil Seal
Shaft Repair on Low Speed Shaft
Need to check and see if the customer has the bott
Hex Head Cap Screw
Breather Assembly
Shim Set
;Shim Set
Shim Set
Oil Slinger
!Shim Set
5/8x3 allen screw
Oil Level Sensor
Oil Temp Sensor
Shipping
Description
11"00e01on Reviewed,ey, • KC Date 13/14/2019
INSPECTION & ESTIMATE Page 7 of 7 ANSI Inspection Form V2.5 - Effective 10/2018
SERVICE ESTIMATE
Customer:
City of Fayetteville, AR
Automatic Engineering
Contact:
Brian Daniels
412 N. Redbud Ave.
Date:
01/03/2019
,> AUTOMATIC
Phone:
479-575-8386
Broken Arrow, OK 74012
ENGINEERING
Fax:
479-684-4730
Phone: 918-585-5703
A COGENT COMPANY
Project: I Fax: 918-585-5707
Quote #: 7013631 Opp #: OP -474527
Dear Brian,
We are pleased to offer the following estimate for your review_
Line No Quantity Description of Unit Net Each Net Ext.
1 1.00 LAT -130
Serial Number - 8625435603
Materials $28,761.72
Labor $11,160.00
Total $39,921.72
Disassembly, Cleaning, Inspection and Estimating Charge
Amount due if this unit is not repaired. An invoice for this charge will
automatically generate within 90 days of this estimate. This charge is
for DCI (Disassembly, Clean and Inspect). All units left at our facility
for more than 6 months will be scrapped unless written notification is
received.
Delivery: 9 - 11 week(s) after receipt of P.O
FOB Point: .................. Shipping Point
Terms of Payment: ...... Net 30
Quote Validity: ............ 30 Days
Thank you for the opportunity to provide you with this estimate. Please let us know how you would like to proceed
Quoted By: Salesrep:
Bryant Peterson Tim Hunt
bpeterson@cogentcompanies.com thunt@aei-inc.com
816-460-1635
$3,720.00
STANDARD TERMS AND CONDITIONS
Price is FOB factory. Price does not include any freight charges. Price does not include any applicable duties or sales tax, use
tax, excise tax, value-added or other similar taxes that may apply to this equipment and/or project. Unless specifically stated,
price does not include manual or automatic controls, starters, protective or signal devices, wiring, anchor bolts, gauges,
vibration isolation devices, installation, startup or testing. +
If the price is included in a proposal, the price is firm for receipt of an order within 30 days of the date shown on the proposal.
Any additional terms and conditions included in the proposal are specifically included in these terms and conditions.
Payment terms are net 30 days with approved credit. An interest charge of 1-1/2% per month will be added to balances over
30 days. Retainage of any invoiced amount is unacceptable unless specifically agreed to by Company at the time of order, and
shall in no case exceed a period of 120 days. If payments are not timely received by Company, and this account is turned over
to an attorney for collections, Customer agrees to pay all reasonable costs and attorney fees incurred in collection of the past
due amounts.
Payment of "commercial transaction" invoices by credit card will be charged a fee based upon Cogenfs average discount rate
for credit card transactions for the prior calendar year. This fee will change annually and is currently 2.55%.
All equipment either rented from or through Company is subject to all of the terms and conditions listed on the back of the
rental contract. Pricing does not include any overtime running of power equipment.
In no event shall Company's obligations and liabilities under this Agreement include any direct, indirect, punitive, special,
incidental or consequential damages or losses that Customer may suffer or incur in connection with this sale, service or rental,
including, but not limited to, loss of revenue or profits, damages or losses as a result of Customer's inability to operate,
perform its obligations to third persons or injuries to goodwill; nor shall Company's liability extend to damages or losses
Customer may suffer or incur as a result of such claims, suits or other proceedings made or instituted against Customer by
third parties. Customer remises, releases and discharges Company from any and all liability or damages which might be
caused by failure to deliver any equipment within the agreed time by Company.
Customer shall be responsible for determining the good operating condition of all materials and equipment prior to accepting
the materials and equipment. NO WARRANTY OR GUARANTEE, EXPRESS OR IMPLIED, INCLUDING ANY
WARRANTY AS TO MERCHANTABILITY OR FITNESS FOR ANY PARTICULAR PURPOSE IS MADE UNLESS
THE SAME IS SPECIFICALLY SET FORTH IN WRITING AND ACCEPTED IN WRITING BY COMPANY, BUT IN
SUCH CASE THE WARRANTY OR GUARANTEE IS LIMITED AS ABOVE PROVIDED. Notwithstanding the
foregoing, Company will pass through to the Customer any warranty provided by the manufacturer of any equipment supplied
by Company.
Customer covenants and agrees to defend, indemnify and hold Company harmless from any claims, damages or liability
arising out of the use, maintenance or delivery of the equipment or materials purchased or rented hereunder. Customer shall
further defend, indemnify and hold Company harmless from any and all damages to third persons or to property caused by
Customer's use or possession of the equipment or materials, to the fullest extent allowable by law.
In connection with a proposal, if Customer has any further questions or comments regarding the proposal, please feel free to
contact Company. If the proposal meets with Customer's approval, please sign, date and mail or fax a copy of the proposal
back to Company's office, and the identified equipment will be ordered and/or scheduled for delivery.
This agreement shall be governed by the laws of the state where the Company's branch office is located from which the
equipment is rented or purchased. Customer further agrees that venue and jurisdiction shall be appropriate in the county in
which Company's branch office is located from which the equipment was rented or purchased. Any provisions hereof which
may prove unenforceable under any law shall not affect the validity of any other provision hereof.
Revised January 2015
INSPECTION & ESTIMATE
COGENT
OGENT Automatic Engineering
Service Center
7013004 -SOD Inspection
Service Order #
7013004
Date
1/3/2018
SUID#
Q-34368
Salesman
Keith Lvett
Customer
City of Fayetteville
Customer Stock #
I L2 - Fuil DCI with Clearances Noted, Sandblasting, Estimate with Pictures, and Repair Report
Contact Name, First
Brian
Service Type
Service
Contact Name, Last
Daniels
Brand
Automatic Engineering
Contact Phone
479-575-8386
Market
Municipal
Contact Cell
1
�II
1
Fluid Being Pumped
N/A Gearbox
Contact Email
Equipment Location/Station
12
(Manufacturer
Lightnin
iModel
LAT -160
Serial #
8625435708
Item Type / Description
Mixer Gear Box
,Additional Items
lCoupling Hub, Auto Lubricater, Piping
Level of Repair
I L2 - Fuil DCI with Clearances Noted, Sandblasting, Estimate with Pictures, and Repair Report
DCI Technician I Chris J I DCI Date 1/11/2019
INSPECTION & ESTIMATE Page 1 of 7 ANSI Inspection Form V2.5 - Effective 10/2018
Pump As Found/Received
Notes:
Gearbox as received for DCI. Lower front & rear
-cover panels were missing when gearbox was
received. Since all 4 gearboxes were missing the
panels, we are assuming that the panels are with
the customer, and were not quoted for
replacement.
i
i
1
�II
1
Jq:
� i •z
. � r
i
INSPECTION & ESTIMATE Page 1 of 7 ANSI Inspection Form V2.5 - Effective 10/2018
INSPECTION & ESTIMATE
7013004 -SOD Inspection
-Shaft
Input Assembly
Inspection Notes
_
No major teeth damage. Assembly spun freely.
- A"
11112
1
f
Work Scope
c
Work 5cope
+ '
Replace bearings, shims, and other wear parts.
,....��
-{
-Shaft
Input
Inspection Notes
Bearing fit is worn out of tolerance.
r
11112
1
f
Work Scope
f r • -
Repair bearing fit.
'
INSPECTION & ESTIMATE Page 2 of 7 ANSI Inspection Form V2.5 - Effective 10/2018
INSPECTION & ESTIMATE
7013004 -SOD Inspection
INSPECTION & ESTIMATE Page 3 of 7 ANSI Inspection Form V2.5 - Effective 10/2018
Upper Bearing
Inspection Notes
e ;
-
d -
Bearing showed normal wear.
i�
Work Scope
Replace with new bearing.
INSPECTION & ESTIMATE Page 3 of 7 ANSI Inspection Form V2.5 - Effective 10/2018
Upper Bearing Housing
Inspection Notes
Housing in good condition, bearing fit was within
tolerance.
Work Scope`:
Cleanup, degrease, and reuse.
e ;
-
d -
INSPECTION & ESTIMATE Page 3 of 7 ANSI Inspection Form V2.5 - Effective 10/2018
INSPECTION & ESTIMATE
Shaft Coupling
Inspection Notes
Shaft hubs and element in good condition.
Work
degrease, & reuse.
Law Speed Shaft
Inspection Notes
Shaft is in good condition, with one bearing fit
being out of tolerance.
Scope
Repair out of tolerance bearing fit, clean & reuse
shaft.
7013004 -SOD Inspection
INSPECTION & ESTIMATE Page 4 of 7 ANSI Inspection Form V2.5 - Effective 10/2018
INSPECTION & ESTIMATE
7013004 -SOD Inspection
INSPECTION & ESTIMATE Page 5 of 7 ANSI Inspection Form V2.5 - Effective 10/2018
Intermediary Gearing
Inspection Notes
Gearing showing some wear to the teeth, but is in
overall good condition.
Work Scope
Clean, degrease, and rebuild.
u
Bearings are showing wear, but have not failed.
INSPECTION & ESTIMATE Page 5 of 7 ANSI Inspection Form V2.5 - Effective 10/2018
Intermediate Bearings
inspection Notes
Bearings are showing wear, but have not failed.
Bearing fits are within tolerance.
r�
Q
.3 �u
�
Work Scope
Clean and degrease shafts and housings. Replace'
As
bearings, shims, and bearing locknuts/lock
washers.
INSPECTION & ESTIMATE Page 5 of 7 ANSI Inspection Form V2.5 - Effective 10/2018
INSPECTION & ESTIMATE
7013004 -SOD Inspection
INSPECTION & ESTIMATE Page 6 of 7 ANSI Inspection Form V2.5 - Effective 10/2018
LOW Speed Shaft Bearing Housing
Inspection Notes
Bearing fits are within tolerance.
�+
.r,
it
Work Scope
'Work Scope
_.
-
Clean and degrease housing. Rebuild with new
wear parts and gaskets.
shims, oil seals, and retaining rings.
i
r..
i
INSPECTION & ESTIMATE Page 6 of 7 ANSI Inspection Form V2.5 - Effective 10/2018
Main Housing
Inspection Notes
Housingcondition. No stripped is in good holes
found.
it
Work Scope
Clean and degrease housing. Rebuild with new
-
=', b • f
wear parts and gaskets.
�C
INSPECTION & ESTIMATE Page 6 of 7 ANSI Inspection Form V2.5 - Effective 10/2018
INSPECTION & ESTIMATE 7013004 -SOD Inspection
Conclusions
Paint Type and Color j I Bin Location I Storage Container (Silver Marker)
Primary Cause of Failure
Normal wear from extended use of the gearbox. Damage to was limited to fits on input and low speed shaft, which will be repaired. Gearbox will be rebuilt
with new wear parts, including bearings, bearing locknuts/lock washers, oil seals, shims, retaining rings, and gaskets (complete parts list below). The oil level
;sensor and oil temperature sensor will be replaced with new units, matching the units installed on previous gearbox repairs. After assembly, the gearboxes
will be painted and shipped back to the customer.
.Additional Notes & Suggestions
All gears are in good condition and will be reused.
Parts Required
PACKING RING
GASKET
SEAL RING
GASKET -COVER PLATE
RETAINING RING
BEARING W33
TAPERED ADAPTER SLEEVE -SPLIT
LOCKNUT & WASHER
OIL SEAL
BEARING W33
RETAINING RING
OIL SEAL
OIL SEAL
SHIM SET
OIL SEAL
GASKET
BEARING
BEARING
RETAINING RING
RETAINING RING
BEARING
THRUST PLATE
SHIM SET
SHIM SET
SHIM SET
NOSE BEARING
BEARING
WASHER
LOCKNUT
OIL SEAL
GASKET
SOCKET HEADSET SCREW
REPAIR SEAL FIT ON SLOW SPEED SHAFT
REPAIR SEAL FIT INPUT SHAFT
OIL LEVEL SENSOR
OIL TEMP SENSOR
HEX HEAD CAP SCREW
Inspection Reviewed By Greg Haggard I Date 1 1/15/2019
INSPECTION & ESTIMATE Page 7 of 7 ANSI Inspection Form V2.5 - Effective 10/2018
SERVICE ESTIMATE
Customer:
City of Fayetteville, AR
Automatic Engineering
Contact:
Brian Daniels
412 N. Redbud Ave.
Date:
12/05/2018
AUTOMATIC
Phone:
479-575-8386
Broken Arrow, OK 74012
ENGINEERING
Fax:
479-684-4730
Phone: 918-585-5703
A COGENT COMPANY
Project:
Fax: 918-585-5707
Quote #:
7013004 Opp #:
Dear Brian,
We are pleased to offer the following estimate for your review.
Line No Quantity Description of Unit Net Each Net Ext.
1 LAT -160
Serial Number - 8625435708
Materials $25,303.09
Labor $11,160.00
Total $36,463.09
Disassembly, Cleaning, Inspection and Estimating Charge
Amount due if this unit is not repaired. An invoice for this charge will
automatically generate within 90 days of this estimate. This charge is
for DCI (Disassembly, Clean and Inspect). All units left at our facility
for more than 6 months will be scrapped unless written notification is
received.
Delivery: ................... 9 - 11 week(s) after receipt of P.O
FOB Point: .................. Shipping Point
Terms of Payment: ...... Net 30
Quote Validity: ............ 30 Days
Thank you for the opportunity to provide you with this estimate. Please let us know how you would like to proceed.
Quoted By: Salesrep:
Bryant Peterson Tim Hunt
bpeterson@cogentcompanies.com thunt@aei-inc.com
816-460-1635
$3,720.00
STANDARD TERMS AND CONDITIONS
Price is FOB factory. Price does not include any freight charges. Price does not include any applicable duties or sales tax, use
tax, excise tax, value-added or other similar taxes that may apply to this equipment and/or project. Unless specifically stated,
price does not include manual or automatic controls, starters, protective or signal devices, wiring, anchor bolts, gauges,
vibration isolation devices, installation, startup or testing.
If the price is included in a proposal, the price is firm for receipt of an order within 30 days of the date shown on the proposal.
Any additional terms and conditions included in the proposal are specifically included in these terms and conditions.
Payment terms are net 30 days with approved credit. An interest charge of 1-1/2% per month will be added to balances over
30 days. Retainage of any invoiced amount is unacceptable unless specifically agreed to by Company at the time of order, and
shall in no case exceed a period of 120 days. If payments are not timely received by Company, and this account is turned over
to an attorney for collections, Customer agrees to pay all reasonable costs and attorney fees incurred in collection of the past
due amounts.
Payment of "commercial transaction" invoices by credit card will be charged a fee based upon Cogenfs average discount rate
for credit card transactions for the prior calendar year. This fee will change annually and is currently 2.55%.
All equipment either rented from or through Company is subject to all of the terms and conditions listed on the back of the
rental contract. Pricing does not include any overtime running of power equipment.
In no event shall Company's obligations and liabilities under this Agreement include any direct, indirect, punitive, special,
incidental or consequential damages or losses that Customer may suffer or incur in connection with this sale, service or rental,
including, but not limited to, loss of revenue or profits, damages or losses as a result of Customer's inability to operate,
perform its obligations to third persons or injuries to goodwill; nor shall Company's liability extend to damages or losses
Customer may suffer or incur as a result of such claims, suits or other proceedings made or instituted against Customer by
third parties. Customer remises, releases and discharges Company from any and all liability or damages which might be
caused by failure to deliver any equipment within the agreed time by Company.
Customer shall be responsible for determining the good operating condition of all materials and equipment prior to accepting
the materials and equipment. NO WARRANTY OR GUARANTEE, EXPRESS OR IMPLIED, INCLUDING ANY
WARRANTY AS TO MERCHANTABILITY OR FITNESS FOR ANY PARTICULAR PURPOSE IS MADE UNLESS
THE SAME IS SPECIFICALLY SET FORTH IN WRITING AND ACCEPTED IN WRITING BY COMPANY, BUT IN
SUCH CASE THE WARRANTY OR GUARANTEE IS LIMITED AS ABOVE PROVIDED. Notwithstanding the
foregoing, Company will pass through to the Customer any warranty provided by the manufacturer of any equipment supplied
by Company.
Customer covenants and agrees to defend, indemnify and hold Company harmless from any claims, damages or liability
arising out of the use, maintenance or delivery of the equipment or materials purchased or rented hereunder. Customer shall
further defend, indemnify and hold Company harmless from any and all damages to third persons or to property caused by
Customer's use or possession of the equipment or materials, to the fullest extent allowable by law.
In connection with a proposal, if Customer has any further questions or comments regarding the proposal, please feel free to
contact Company. If the proposal meets with Customer's approval, please sign, date and mail or fax a copy of the proposal
back to Company's office, and the identified equipment will be ordered and/or scheduled for delivery.
This agreement shall be governed by the laws of the state where the Company's branch office is located from which the
equipment is rented or purchased. Customer further agrees that venue and jurisdiction shall be appropriate in the county in
which Company's branch office is located from which the equipment was rented or purchased. Any provisions hereof which
may prove unenforceable under any law shall not affect the validity of any other provision hereof.
Revised January 2015
INSPECTION & ESTIMATE
7013634 -SOD Inspection
N
Automatic Engineering
Service Center
Notes:
Service Order #
7013634
Date
1/3/2018
SUID #
Q-36430
Salesman
Keith Lovett
Customer
City of Fayetteville
Customer Stock #
the customer, and were not quoted for
Contact Name, First
Brian
Service Type
Service
Contact Name, Last
Daniels
Brand
Automatic Engineering
Contact Phone
479-575-8386
Market
Municipal
Contact Cell
Fluid Being Pumped
N/A Gearbox
Contact Email
Equipment Location/Station
19
�
'Manufacturer
Lightnin
i�
(Model
LAT -130
Serial #
8625435601
Item Type / Description
Mixer Gear Box
Additional Items
Coupling Hub, Auto Lubricater, Piping
Level of Repair
I L2 - Full DCI with Clearances Noted, Sandblasting, Estimate with Pictures, and Repair Report
DCI Technician I Chris J I DCI Date 1/22/2019
INSPECTION & ESTIMATE Page 1 of 7 ANSI Inspection Form V2,5 - Effective 10/2018
Pump As Found/Received
Notes:
Gearbox as received for DCI. Lower front & rear
cover panels were missing when gearbox was
received. Since all 4 gearboxes were missing the
panels, we are assuming that the panels are with
the customer, and were not quoted for
replacement.
�
Iy
i�
I�
ti
5. •.3f
- - a
w,
INSPECTION & ESTIMATE Page 1 of 7 ANSI Inspection Form V2,5 - Effective 10/2018
INSPECTION & ESTIMATE
7013634 -SOD Inspection
INSPECTION & ESTIMATE Page 2 of 7 ANSI Inspection Form V2.5 - Effective 10/2018
Input Assembly
Inspection Notes
a
No major teeth damage. Assembly spun freely.
„Y
j
■ i
r .r
Work Scope
r
Replace bearings, shims, and other wear parts
R
_ 1
INSPECTION & ESTIMATE Page 2 of 7 ANSI Inspection Form V2.5 - Effective 10/2018
Input Shaft
Inspection Notes
•Groove worn into shaft at lip seal fit.
'Work Scope
Repair lip seal fit.
a
INSPECTION & ESTIMATE Page 2 of 7 ANSI Inspection Form V2.5 - Effective 10/2018
INSPECTION & ESTIMATE
7013634 -SOD Inspection
INSPECTION & ESTIMATE Page 3 of 7 ANSI Inspection Form V2 5 - Effective 10/2018
Upper Bearing
Inspection Notes
Bearing showed normal wear.
Housing in good condition, bearing fit was within
Work Scope
Replace with new bearing.
-
Work Scope
Cleanup, degrease, and reuse.
-
INSPECTION & ESTIMATE Page 3 of 7 ANSI Inspection Form V2 5 - Effective 10/2018
Upper Bearing Housing
Inspection Notes:^.
Housing in good condition, bearing fit was within
tolerance.
-
Work Scope
Cleanup, degrease, and reuse.
-
„ 4 l - S•.
INSPECTION & ESTIMATE Page 3 of 7 ANSI Inspection Form V2 5 - Effective 10/2018
INSPECTION & ESTIMATE
7013634 -SOD Inspection
INSPECTION & ESTIMATE Page 4 of 7 ANSI Inspection Form V2.5 - Effective 10/2018
Shaft Coupling
Row Speed Shaft
Inspection Notes
Inspection Notes
Shaftis in good condition.
Shaft hubs and element in good condition,
t
Work Scope
'Work Scope
Clean, degrease, & reuse..
'r -
INSPECTION & ESTIMATE Page 4 of 7 ANSI Inspection Form V2.5 - Effective 10/2018
Row Speed Shaft
Inspection Notes
Shaftis in good condition.
Work Scope
Clean & reuse shaft.
INSPECTION & ESTIMATE Page 4 of 7 ANSI Inspection Form V2.5 - Effective 10/2018
INSPECTION & ESTIMATE
7013634 -SOD Inspection
INSPECTION & ESTIMATE Page 5 of 7 ANSI Inspection Form V2.5 - Effective 10/2018
Intermediary Gearing
Inspection Notes
Gearing showing some wear to the teeth, but is in
overall good condition.
17 -
Work Scope
Clean, degrease, and rebuild.
--------
Y_.. +Y
Bearings are showing wear, but have not failed.
r .•
INSPECTION & ESTIMATE Page 5 of 7 ANSI Inspection Form V2.5 - Effective 10/2018
Intermediate Bearings
Inspection Notes
--------
Bearings are showing wear, but have not failed.
Bearing fits are within tolerance.
[-..
r
Work Scope
i
Clean and degrease shafts and housings. Replace
bearings, shims, and bearing locknuts/lock
' at
washers.AW
r
INSPECTION & ESTIMATE Page 5 of 7 ANSI Inspection Form V2.5 - Effective 10/2018
INSPECTION & ESTIMATE
7013634 -SOD Inspection
INSPECTION & ESTIMATE Page 6 of 7 ANSI Inspection Form V2.5 - Effective 10/2018
Low Speed Shaft Bearing Housing
Inspection Notes,
+'
Bearing fits are within tolerance.
repaired, due to spinning of the outer bearing
race. Clearance is at 0.0035", and should be no
more than 0.002".
Work Scope
Repair bearing fit. Clean and degrease housing.
Work Scope
4.
Clean and degrease housing. Rebuild with new
shims, oil seals, and retaining rings.
_
i
56
INSPECTION & ESTIMATE Page 6 of 7 ANSI Inspection Form V2.5 - Effective 10/2018
Main Housing
Inspectlon;Note s ,
+'
Low speed shaft lower bearing fit will need to be
repaired, due to spinning of the outer bearing
race. Clearance is at 0.0035", and should be no
more than 0.002".
Work Scope
Repair bearing fit. Clean and degrease housing.
Rebuild with new wear parts and gaskets.
'
INSPECTION & ESTIMATE Page 6 of 7 ANSI Inspection Form V2.5 - Effective 10/2018
INSPECTION & ESTIMATE 7013634 -SOD Inspection
Conclusions
Paint Type and Color lGreen I Bin Location IStorage Container/Light Blue Dot
Primary Cause of Failure
Normal wear from extended use of the gearbox. Damage to was limited to groove on low speed shaft and oversize bearing fit on housing, which will both be
repaired. Gearbox will be rebuilt with new wear parts, including bearings, bearing locknuts/lock washers, oil seals, shims, retaining rings, and gaskets
(complete parts list below). The oil level sensor and oil temperature sensor will be replaced with new units, matching the units installed on previous gearbox
repairs. After assembly, the gearboxes will be painted and shipped back to the customer.
Additional Notes & Suggestions
All gears are in good condition and will be reused.
Parts Required
REPAIR ID BORE ON SLOW SPEED SHAFT LOWER BE SANDBLASTING
PACKING RING
GASKET
SEAL RING
GASKET -COVER PLATE
GREASE RETAINER
RETAINING RING
BEARING
TAPERED ADAPTER SLEEVE -SPLIT
ADAPTER SLEEVE -SOLID
LOCKNUT AND WASHER
OILSEAL
BEARING
RETAINING RING
OIL SEAL
OIL SEAL
OIL SEAL
GASKET
BEARING
BEARING
RETAINING RING
RETAING RING
BEARING
NOSE BEARING
BEARING
WASHER
LOCKNUT
OIL SEAL-C/R 22361
GASKET
.SHIM SET
SHIM SET
SHIM SET
SHIM SET
OIL TEMPERATURE SENSOR
OIL LEVEL CONTROL SWITCH
TUBING
CONNECTOR
REPAIR SEAL FIT ON INPUT SHAFT
Inspection Reviewed By I Greg Hoggard I Date 1 1/22/2019
INSPECTION & ESTIMATE Page 7 of 7 ANSI Inspection Form V2.5 - Effective 10/2018
SERVICE ESTIMATE
Customer:
City of Fayetteville, AR
Automatic Engineering
Contact :
Brian Daniels
412 N. Redbud Ave.
Date:
01/03/2019
, AUTOMATIC
Phone:
479-575-8386
Broken Arrow, OK 74012
ENGINEERING
Fax:
479-684-4730
Phone: 918-585-5703
A COGENT COMPANY
Project: I Fax: 918-585-5707
Quote #: 7013634 Opp #: OP -474531
Dear Brian,
We are pleased to offer the following estimate for your review
Line No Quantity i Description of Unit I Net Each I Net Ext.
1 1.00 LAT -130
Serial Number - 8625435601
Materials $19,419.21
Labor $11,180.00
Total $30,579.21
Disassembly, Cleaning, Inspection and Estimating Charge
Amount due if this unit is not repaired. An invoice for this charge will
automatically generate within 90 days of this estimate. This charge is
for DCI (Disassembly, Clean and Inspect). All units left at our facility
for more than 6 months will be scrapped unless written notification is
received.
Delivery: ................... 9 - 11 week(s) after receipt of P.O.
FOB Point: .................. Shipping Point
Terms of Payment: ...... Net 30
Quote Validity: ............ 30 Days
Thank you for the opportunity to provide you with this estimate. Please let us know how you would like to proceed.
Quoted By: Salesrep:
Bryant Peterson Tim Hunt
bpeterson@cogentcompanies.com thunt@aei-inc.com
816-460-1635
$3,720.00
STANDARD TERMS AND CONDITIONS
Price is FOB factory. Price does not include any freight charges. Price does not include any applicable duties or sales tax, use
tax, excise tax, value-added or other similar taxes that may apply to this equipment and/or project. Unless specifically stated,
price does not include manual or automatic controls, starters, protective or signal devices, wiring, anchor bolts, gauges,
vibration isolation devices, installation, startup or testing.
If the price is included in a proposal, the price is firm for receipt of an order within 30 days of the date shown on the proposal.
Any additional terms and conditions included in the proposal are specifically included in these terms and conditions.
Payment terms are net 30 days with approved credit. An interest charge of 1-1/2% per month will be added to balances over
30 days. Retainage of any invoiced amount is unacceptable unless specifically agreed to by Company at the time of order, and
shall in no case exceed a period of 120 days. If payments are not timely received by Company, and this account is turned over
to an attorney for collections, Customer agrees to pay all reasonable costs and attorney fees incurred in collection of the past
due amounts.
Payment of "commercial transaction" invoices by credit card will be charged a fee based upon Cogenfs average discount rate
for credit card transactions for the prior calendar year. This fee will change annually and is currently 2.55%.
All equipment either rented from or through Company is subject to all of the terms and conditions listed on the back of the
rental contract. Pricing does not include any overtime running of power equipment.
In no event shall Company's obligations and liabilities under this Agreement include any direct, indirect, punitive, special,
incidental or consequential damages or losses that Customer may suffer or incur in connection with this sale, service or rental,
including, but not limited to, loss of revenue or profits, damages or losses as a result of Customer's inability to operate,
perform its obligations to third persons or injuries to goodwill; nor shall Company's liability extend to damages or losses
Customer may suffer or incur as a result of such claims, suits or other proceedings made or instituted against Customer by
third parties. Customer remises, releases and discharges Company from any and all liability or damages which might be
caused by failure to deliver any equipment within the agreed time by Company.
Customer shall be responsible for determining the good operating condition of all materials and equipment prior to accepting
the materials and equipment. NO WARRANTY OR GUARANTEE, EXPRESS OR IMPLIED, INCLUDING ANY
WARRANTY AS TO MERCHANTABILITY OR FITNESS FOR ANY PARTICULAR PURPOSE IS MADE UNLESS
THE SAME IS SPECIFICALLY SET FORTH IN WRITING AND ACCEPTED IN WRITING BY COMPANY, BUT IN
SUCH CASE THE WARRANTY OR GUARANTEE IS LIMITED AS ABOVE PROVIDED. Notwithstanding the
foregoing, Company will pass through to the Customer any warranty provided by the manufacturer of any equipment supplied
by Company.
Customer covenants and agrees to defend, indemnify and hold Company harmless from any claims, damages or liability
arising out of the use, maintenance or delivery of the equipment or materials purchased or rented hereunder. Customer shall
further defend, indemnify and hold Company harmless from any and all damages to third persons or to property caused by
Customer's use or possession of the equipment or materials, to the fullest extent allowable by law.
In connection with a proposal, if Customer has any further questions or comments regarding the proposal, please feel free to
contact Company. If the proposal meets with Customer's approval, please sign, date and mail or fax a copy of the proposal
back to Company's office, and the identified equipment will be ordered and/or scheduled for delivery.
This agreement shall be governed by the laws of the state where the Company's branch office is located from which the
equipment is rented or purchased. Customer further agrees that venue and jurisdiction shall be appropriate in the county in
which Company's branch office is located from which the equipment was rented or purchased. Any provisions hereof which
may prove unenforceable under any law shall not affect the validity of any other provision hereof.
Revised January 2015
INSPECTION & ESTIMATE
7013636 -SOD Inspection
Manufacturer
COGENT
Automatic Engineering
Service Center
LAT -130
Serial #
8625435604
Item Type / Description
Service Order #
7013636
Date
1/3/2018
SUID #
Q-36432
Salesman
Keith Lovett
Customer
City of Fayetteville
Customer Stock #
Contact Name, First Brian
Service Type
Service
Contact Name, Last Daniels
Brand
Automatic Engineering
Contact Phone
479-575-8386
Market
Municipal
Contact Cell
Fluid Being Pumped
N/A Gearbox
Contact Email
_ .,tib � •�_ •��. _
Equipment Location/Station
14
Manufacturer
Lightnin
Model
LAT -130
Serial #
8625435604
Item Type / Description
Mixer Gear Box
Additional Item
lCoupling Hub, Auto Lubricater, Piping
Level of Repair
1-2 - Full DCI with Clearances Noted, Sandblasting, Estimate with Pictures, and Repair Report
DCI Technician I I Luke Steinhauser JDCI Date 1/10/2019
INSPECTION & ESTIMATE Page 1 of 7 ANSI Inspection Form V2.5 - Effective 10/2018
Pump As Found/Received
Notes:
Gearbox as received for DCI. Lower front & rear
cover panels were missing when gearbox was
received. Since all 4 gearboxes were missing the
panels, we are assuming that the panels are with
the customer, and were not quoted for
_
replacement.
_ .,tib � •�_ •��. _
I r
�.. r���!Lfl�
k �y
c Y '
INSPECTION & ESTIMATE Page 1 of 7 ANSI Inspection Form V2.5 - Effective 10/2018
INSPECTION & ESTIMATE
7013636 -SOD Inspection
INSPECTION & ESTIMATE Page 2 of 7 ANSI Inspection Form V2.5 - Effective 10/2018
Input Shaft
Inspection Notes
,Oil seal has worn a groove into the shaft which will
need to be repaired. Teeth are in good condition.
Work Scope
Repair seal fit.
Input Assembly
-' - - --
i
�, .._..
Inspection Notes
_ I
No major teeth damage. Assembly spun freely.
Work scope
Replace bearings, shims, and other wear parts.
+a
INSPECTION & ESTIMATE Page 2 of 7 ANSI Inspection Form V2.5 - Effective 10/2018
Input Shaft
Inspection Notes
,Oil seal has worn a groove into the shaft which will
need to be repaired. Teeth are in good condition.
Work Scope
Repair seal fit.
-' - - --
i
�, .._..
INSPECTION & ESTIMATE Page 2 of 7 ANSI Inspection Form V2.5 - Effective 10/2018
INSPECTION & ESTIMATE
7013636 -SOD Inspection
INSPECTION & ESTIMATE Page 3 of 7 ANSI Inspection Form V2.5 - Effective 10/2018
Upper Bearing
Inspection Notes
Bearing showed normal wear.
'
tolerance.
r
Work Scope�-
1
Replace with new bearing.
Cleanup, degrease, and reuse.
y4.
INSPECTION & ESTIMATE Page 3 of 7 ANSI Inspection Form V2.5 - Effective 10/2018
Upper Bearing Housing
Inspection Notes
Housing in condition, bearing fit was within
good
tolerance.
Work Scope
Cleanup, degrease, and reuse.
'Y
INSPECTION & ESTIMATE Page 3 of 7 ANSI Inspection Form V2.5 - Effective 10/2018
INSPECTION & ESTIMATE
7013636 -SOD Inspection
INSPECTION & ESTIMATE Page 4 of 7 ANSI Inspection Form V2.5 - Effective 10/2018
Shaft Coupling
Inspection Notes-,-,�-�.
One the hubs is damaged the
Low Speed Shaft
of at outer slots and
Inspection Notes
Shaft is in good condition.
is not repairable.',f.
_ t
-- - --.- - —
r
t
�-'• iS .� .ti .. ii
vow
.r�t
i
Work Scope
Replace one hub. Clean, degrease, & reuse other
hubs.
Clean & reuse shaft.
INSPECTION & ESTIMATE Page 4 of 7 ANSI Inspection Form V2.5 - Effective 10/2018
Low Speed Shaft
Inspection Notes
Shaft is in good condition.
-- - --.- - —
r
t
�-'• iS .� .ti .. ii
'Work Scope
Clean & reuse shaft.
INSPECTION & ESTIMATE Page 4 of 7 ANSI Inspection Form V2.5 - Effective 10/2018
INSPECTION & ESTIMATE
7013636 -SOD Inspection
INSPECTION & ESTIMATE Page 5 of 7 ANSI Inspection Form V2.5 - Effective 10/2018
Intermediary Gearing
Inspection Notes
Oil seal has worn a groove into the shaft that will
r
need repaired. Gearing showing some wear to the
t
teeth, but is in overallgood condition.?
-
—°
Bearing fits are within tolerance.
— w
..
n
Work Scope
Repair oil seal groove. Clean, degrease, and
.R.
rebuild.
Work Scope
Clean and degrease shafts and housings. Replace
-.0
5
„�',:•.
INSPECTION & ESTIMATE Page 5 of 7 ANSI Inspection Form V2.5 - Effective 10/2018
Intermediate Bearings
Inspection Notes
Bearings are showing wear, but have not failed
—°
Bearing fits are within tolerance.
— w
..
n
4D
-
r ..
Work Scope
Clean and degrease shafts and housings. Replace
-.0
5
„�',:•.
bearings, shims, and bearing locknuts/lock
r —
washers.
INSPECTION & ESTIMATE Page 5 of 7 ANSI Inspection Form V2.5 - Effective 10/2018
INSPECTION & ESTIMATE
7013636 -SOD Inspection
INSPECTION & ESTIMATE Page 6 of 7 ANSI Inspection Form V2.5 - Effective 10/2018
Main Housing"",,
!Inspection Notes
Low Speed Shaft Bearing Housing
1
Lower bearing spun in bearing fit.
Inspection Notes
'Work Scope
Repair lower bearing fit to restore clearances.
Bearing fits are within tolerance.
wear parts and gaskets.
� *f
•.� rte- �..
;r
i
'Work Scope
Clean and degrease housing. Rebuild with new
:shims, oil seals, and retaining rings.
z
-'
INSPECTION & ESTIMATE Page 6 of 7 ANSI Inspection Form V2.5 - Effective 10/2018
Main Housing"",,
!Inspection Notes
1
Lower bearing spun in bearing fit.
'Work Scope
Repair lower bearing fit to restore clearances.
Clean and degrease housing. Rebuild with new
wear parts and gaskets.
INSPECTION & ESTIMATE Page 6 of 7 ANSI Inspection Form V2.5 - Effective 10/2018
INSPECTION & ESTIMATE 7013636 -SOD Inspection
Conclusions
Pail)t Type and Color Ivista green ameralock 113in Location I Cony box - Red Code
Cause of Failure
Normal wear from extended use of the gearbox. Damage to was limited to fits on input and low speed shaft, which will be repaired. Gearbox will be rebuilt
with new wear parts, including bearings, bearing locknuts/lock washers, oil seals, shims, retaining rings, and gaskets (complete parts list below). The oil level
sensor and oil temperature sensor will be replaced with new units, matching the units installed on previous gearbox repairs. The top cover assembly which
covers the head bearing was severly rusted, and will be replaced. After assembly, the gearboxes will be painted and shipped back to the customer.
Additional Notes & Suggestions
All gears are in good condition and will be reused.
Parts Required
Coupling Half
Oil Seal
Oil Seal
Oil Seal
Gasket
Breather Assembly
Bearing
Bearing
Bearing
Heax Head Capscrew
Hex Head Capscrew
Nose Bearing
Bearing
Locknut
Oil Seal
•Gasket
Shim Set
Shim Set
:Shim Set
Shim Set
Packing Ring
Gasket
Seal Ring
Gasket - Cover Plate
Retaining Ring
Top Cover Assembly
Bearing
'Tapered Adapter Sleeve - Split
Adapter Sleeve -Solid
Locknut & Lockwasher
Oil Seal
Bearing
Repair Bearing Housing Fit
Low Speed Shaft Fit Repair
Input Shaft Repair
Sandblasting
Freight
Oil Temperature Sensor
Oil Level Sensor
inspection Reviewed Ely Greg Hoggard jDate 1/15/2019
INSPECTION & ESTIMATE Page 7 of 7 ANSI Inspection Form V2.5 - Effective 10/2018
SERVICE ESTIMATE
Customer:
City of Fayetteville, AR
Automatic Engineering
Contact:
Brian Daniels
412 N. Redbud Ave.
Date:
01/03/2019
•rq AUTOMATIC
Phone:
479-575-8386
Broken Arrow, OK 74012
ENGINEERING
Fax:
479-684-4730
Phone: 918-585-5703
A COGENT COMPANY
Project: I Fax: 918-585-5707
Quote #: 7013636 Opp #: OP -474534
Dear Brian,
We are pleased to offer the following estimate for your review.
Line No Quantity Description of Unit Net Each Net Ext.
1 1.00 LAT -130
Serial Number - 8625435604
Materials $22,328.31
Labor $11,160.00
Total $33,488.31
Disassembly, Cleaning, Inspection and Estimating Charge
Amount due if this unit is not repaired. An invoice for this charge will
automatically generate within 90 days of this estimate. This charge is
for DCI (Disassembly, Clean and Inspect). All units left at our facility
for more than 6 months will be scrapped unless written notification is
received.
Delivery: 9 - 11 week(s) after receipt of P.O.
FOB Point: .................. Shipping Point
Terms of Payment: ...... Net 30
Quote Validity: ............ 30 Days
Thank you for the opportunity to provide you with this estimate. Please let us know how you would like to proceed
Quoted By: Salesrep:
Bryant Peterson Tim Hunt
bpeterson@cogentcompanies.com thunt@aei-inc.com
816-460-1635
$3,720.00
STANDARD TERIVIS AND CONDIT]UNS
Price is FOB factory. Price does not include any freight charges. Price does not include any applicable duties or sales tax, use
tax, excise tax, value-added or other similar taxes that may apply to this equipment and/or project. Unless specifically stated,
price does not include manual or automatic controls, starters, protective or signal devices, wiring, anchor bolts, gauges,
vibration isolation devices, installation, startup or testing.
If the price is included in a proposal, the price is firm for receipt of an order within 30 days of the date shown on the proposal.
Any additional terms and conditions included in the proposal are specifically included in these terms and conditions.
Payment terms are net 30 days with approved credit. An interest charge of 1-1/2% per month will be added to balances over
30 days. Retainage of any invoiced amount is unacceptable unless specifically agreed to by Company at the time of order, and
shall in no case exceed a period of 120 days. If payments are not timely received by Company, and this account is turned over
to an attorney for collections, Customer agrees to pay all reasonable costs and attorney fees incurred in collection of the past
due amounts.
Payment of "commercial transaction" invoices by credit card will be charged a fee based upon Cogenfs average discount rate
for credit card transactions for the prior calendar year. This fee will change annually and is currently 2.55%.
All equipment either rented from or through Company is subject to all of the terms and conditions listed on the back of the
rental contract. Pricing does not include any overtime running of power equipment.
In no event shall Company's obligations and liabilities under this Agreement include any direct, indirect, punitive, special,
incidental or consequential damages or losses that Customer may suffer or incur in connection with this sale, service or rental,
including, but not limited to, loss of revenue or profits, damages or losses as a result of Customer's inability to operate,
perform its obligations to third persons or injuries to goodwill; nor shall Company's liability extend to damages or losses
Customer may suffer or incur as a result of such claims, suits or other proceedings made or instituted against Customer by
third parties. Customer remises, releases and discharges Company from any and all liability or damages which might be
caused by failure to deliver any equipment within the agreed time by Company.
Customer shall be responsible for determining the good operating condition of all materials and equipment prior to accepting
the materials and equipment. NO WARRANTY OR GUARANTEE, EXPRESS OR IMPLIED, INCLUDING ANY
WARRANTY AS TO MERCHANTABILITY OR FITNESS FOR ANY PARTICULAR PURPOSE IS MADE UNLESS
THE SAME IS SPECIFICALLY SET FORTH IN WRITING AND ACCEPTED IN WRITING BY COMPANY, BUT IN
SUCH CASE THE WARRANTY OR GUARANTEE IS LIMITED AS ABOVE PROVIDED. Notwithstanding the
foregoing, Company will pass through to the Customer any warranty provided by the manufacturer of any equipment supplied
by Company.
Customer covenants and agrees to defend, indemnify and hold Company harmless from any claims, damages or liability
arising out of the use, maintenance or delivery of the equipment or materials purchased or rented hereunder. Customer shall
further defend, indemnify and hold Company harmless from any and all damages to third persons or to property caused by
Customer's use or possession of the equipment or materials, to the fullest extent allowable by law.
In connection with a proposal, if Customer has any further questions or comments regarding the proposal, please feel free to
contact Company. If the proposal meets with Customer's approval, please sign, date and mail or fax a copy of the proposal
back to Company's office, and the identified equipment will be ordered and/or scheduled for delivery.
This agreement shall be governed by the laws of the state where the Company's branch office is located from which the
equipment is rented or purchased. Customer further agrees that venue and jurisdiction shall be appropriate in the county in
which Company's branch office is located from which the equipment was rented or purchased. Any provisions hereof which
may prove unenforceable under any law shall not affect the validity of any other provision hereof.
Revised January 2015
MAR 2 5 2019
NORTHWEST ARKANSAS CITY of FAYEL LVILL ,
C171
CLERK'S aFACE
IOCoazette
AFFIDAVIT OF PUBLICATION
I Cathy Staggs, do solemnly swear that I am the Accounting Manager of the
Northwest Arkansas Democrat -Gazette, printed and published in
Washington County and Benton County, Arkansas, and of bona fide
circulation, that from my own personal knowledge and reference
to the files of said publication, the advertisement of:
CITY OF FAYETTEVILLE
Ord. 6159
Was inserted in the Regular Edition on:
March 14, 2019
Publication Charges: $ 79.30
Cathy Stag(y
Subscribed and sworn to before me
This G1 day of A�L(A,, 2019.
V,,
�,&
Notary Public
My Commission Expires: Z Z�I Zu
CATNY INILES
Artcalnsas - Benton 0001y
ary pt,111lr. - cc7tnmx 1231+
4y (-'gni11-0541Wj E;:p1r�s f b 7f+
**NOTE**
Please do not pay from Affidavit.
Invoice will be sent.
Ordinance: 6159
File Number: 2019-0117
AUTOMATIC ENGINEERING:
AN ORDINANCE TO WAIVE COMPETITIVE
BIDDING AND TO ACCEPT A REPAIR
QUOTE OF $140,452.33, PLUS APPLICABLE
TAXES, FROM AUTOMATIC
ENGINEERING TO REPAIR FOUR
AGITATOR GEARBOXES FOR THE PAUL
R. NOLAND WASTEWATER TREATMENT
FACILITY
WHEREAS, formal sealed bidding is not
necessary for the repair of "hidden or unknown
damages'% and
WHEREAS, Automatic Engineering has taken
apartand examined floor agitator gearboxes and
determined that repair of these gearboxes would
cost $140,452,33 plus applicable taxes,
NOW, THEREFORE, BE IT ORDAINED BY
THE CITY COUNCIL OF THE CITY OF
FAYETTEVILLE, ARKANSAS:
Section 1. That the City Council of the City of
Fayetteville, Arkansas hereby determines that,
because of Ark. Code Ann, $I9-I1-203(14)(EE),
the repair of "hidden or unknown damages" does
not require formal competitive bidding and
therefore, waives competitive bidding and
accepts Automatic Engineering's repair quote of
$140,452.33 (plus any applicable taxes) and
authorizes the payment of that amount.
PASSED and APPROVED on 3/5/2019
Approved:
Lioneld Jordan, Mayor
Attest:
Sondra E. Smith, City Clerk Treasurer
74872912 Mar, 14, 2019