Loading...
HomeMy WebLinkAboutOrdinance 1009 a. OPDPW!CE NO. 1009 National ATI ORDIMANC= ADOPTINTO Tit: COX: OF TH7XMI=. FIRS PROTSCTIOIJ AS''OCIATIO" DESICrArm AS PAMPHLET N . F' . P .A . No . 30-L3 I14 PART, AYD Ri;LATINO TO THE ^TOSACE , f ANDLINC , and USE OF FLAL4.".ADL: LI:UIDS . tYll's?MAS, the City Council of the City of Fayetteville , Arkansas , caused a notice to be published that it had under consideration the adoption of an Ordin- ance relating to the storage , handling, and use of flamaable liquids as set forth in the code of the National Fire Protection Association designated as " Pam- phlet NFPA No . 30-L" , and IiH MAS , the requisite number of copies of said code were kept on file as provided by Act 267 of the Acts of t.rkansaa for the year 1949 , cnd there have been no protests or sue€estiann or requests for discussion , and 4. H'3REAS , the City Council of the City of Fayetteville , Arkansas , finds that it is the best interest of the City of Fayetteville . that the above code of the National Fire Protection Arsociaticn desif:nat=d as "Pamphlet VF'PA No . 30-L , be substantially adopted except for those amendments hereinafter set forth : NO4i , THEREFORE , BE IT ORDAINED BY TH"i. CITY COUNCIL OF THE CITY OF FAYETTWILM , ARKANSAS : SECTION 1 . That the code of the National Fire Protection Association, deeig- nated as Pamphlet NFPA No . 30-L, relating tothe storage , handling, and use of flamjn- g able liquids , is hereby adopted for the City of Fayetteville , Arkansas , except as hereinafter provided . t SECTIR'• 2 . That Section 104. 06 of Pamphlet NFPA No. 3C-L be and the same is hereby amended to read as follows : "104.06 . "Chief" shall moan the City Enr.ineer and shall include arpr officer, member, or imopector deputized for the pur?oses of this ordinance by the chief. The Chief of the Fire Department shall serve the chief in an advisory caps ;ity for the purposes of this ordinance . SECTION 3 . That Section 104 . 07 of Pamphlet MFH, Mo. 30-L be and the same is here- by amdnded to read as follows : "104. 07 . "City Council" shall mean the duly elected and constituted City Council of the City of Fayetteville, Arkansas . S3CThDN 4. That Section 202 . 01 of Pamphlet *'FPA No . 30-L be and the same is hereby deleted and omitted from the operation of tide ordinance . SECTION 5. That Section 1003 . Ponalti :s . of Pamphlet :•'FPA Flo. 30-L be and the same is hereby amended to read as follows : 111003 . Penalties : Any person whoshall fail to co:aply with the provisions of this ordinance or with an order of the Chief issued pursuant thereto and from which no a.apeal has been talcen, or u:ith such an order as affirmed or modified by the City Council or by a court of competent jurisdiction, within the time fixed therein, shall be fined not less than One (u1. 00 ) Dollar nor more than Twenty-Five (3225. 00 ) Dollars . The :imposition of one penalty for the violation of such order shall not excuse the violation or pe =it it to continue , and each succeedirr. day of violation of the terms MICROFILMLD DATE OCT 6 1918 REED - and provisions of this ordimince shall constitute a separate offense . sEcTion 6 . All ordinances or parts of ordioa.nces in conflict herewith are hereby repealed, and this Ordinance being necessary for the preservation of the public health, peace arc; safety, an emerpency is hereby declared to eyist, and this Ordinance shall be in full force anal effect from and after its passa€-c , approval, and publication. Passed and approved this 22 day of October, 1951 . Yowe 1 c . Rhea, AMEST: PRC ghee , City C er f NOT TO BE. REMOVED FROM CLERKIS OFFICE `. a part of Ordinance No , 1009/ I Stora ' et Handling ane Use or 1 FLAMMABLE LIQUIDS 1951 �. Second Printine a AFP t Price: 50 cents i Discount for Quantities NATIONAL FIRE PROTECTION ASSOCIATION i� International 60 Batterymarch St., Boston 10, Mau., U.S.A. J 8-721-7-81 W.A.S. Copyrl8ht, 1881 Printed In V.S.A. National Fire Protection Anociation 1951 SUGGESTED ORDINANCE for the STORAGE, HANDLING AND USE OF FLAMMABLE LIQUIDS (PREPARED FOR USE AS A MUNICIPAL ORDINANCE) Page F?reword .................................................................................................................... 4 I General Provisions .................................................................................. S IIStorage ...................................................................................................... 9 III Piping Valves and Fittings.................... ................. 19 IVBulk Plants ................................................................................................ 20 VService Stations ...............................--..................................................... 23 VI Commercial and Industrial Establishments............. ---................... 25 VIIProcessing Plants .................................................................................... 29 VIII Storage and Use of Flammable Liquids as Fuel for Heating and PowerDevices ................................................................................ 31 IX Refineries and Other Plants Storing and Handling Crude ., Petroleum .............:............................................................................ 32 X Modification, Appeals, Penalties, etc............._................ ...... .......... . 33 APPENDIXES A. Rooms, Cabinets and Outside Houses for the Storage of Flam- mableLiquids ..........--.................................................................... 34 B. Protection of Tanks Containing Flammable Liquids in Loca- tions That May Be Flooded.......................................................... 40 i G Recommended Procedure for the Abandonment or Removal of Service Station Underground Tanks........................----..... 44 List of Published Standards Included in the Ordinance...................... 46 l .. National Fire Protection Association The National Fire Protection Association was organised in 1896 to jersects the science and improve the methods of lire protection and prsosntion, to obtain and circulate information on these subjects and to secure the cooperation of its members in establishing proper safeguards against lose of life and property by fire. This pamphlet is one of a large numbs: of publications on fire Safety issued by the Association. NFPA COMhIITTEE ON FLAMMABLE LIQUIDS. H. L. Mixga. Chairman, 4287 Osage Ave., Philadelphia 4, Pa. H. E. NHwxlq Secretary, National Board of Fire Underwriters, 86 John Street, New York, N. Y. STANLer EAma, Flammable Liquids Engineer, National Fire Protection Association, 60 Batterymarch St., Boston 10, Mase. W. J. BAHmt, A. J. KaAssam, Conference of Special Risk Under- U. S. Bureau of Mines. writers. W. S. MARSH, Hsmoscr R. BoOAsous, Factory Mutual Engineering Div. Fire Insurance Rating Organization of F. J. MCCLAtN, New Jersey. Factory Insurance Association. C. H. BUNN, JR, W. G. MCKENNA, American Petroleum Institute Bureau of Explosives, Association of S. L. BURCHER, American Railroads. New England Fire Insurance Rating C. D. Nomas, Association. American Petroleum Institute. HAnow CROUCH, H. Nmmis Pre, Eastman Kodak Co. South-Eastern Underwriters Aeon. H. P. Dixey, ARNOLD C. RENNER, Rating and Fire Prevention Bureau. NFPA Fire Marshals' Section. W. H. DOYLH, FRANK SLUZE, Factory Insurance Association. National Petroleum Association. EDWARD W. HALL, ALLAN R. SMITH, NFPA Fire Marshals' Section. Steel Tank Institute, PetroleuN, D. V. STROUT, R. T. American Petroleum Institute. Ohio Petroleum Marketers Asan. E. F. TAstss, JAmsa E. HILL, Underwriters' Laboratories of Canada. Western Oil and Gas Asan. Faro A. TuAsx, O. W. JOHNSON, Oil Insurance Association. American Petroleum Institute J. H. WrrrH, D. F. JONM' Underwritem' Laboratories, Inc. Institute of Cooking and Heating Ap- J. MILTON WRIGHT. pliance Manufacturers. Associated Reciprocal Exchanges. G. T. KAUFMAN, T. H, WmCH'T, Oil-Heat Institute of America Ohio Inspection Bureau. CONFERENCE COMMITTER ON ORDINANCE. C. H. BUNN, JR„ Chairman, Standard Oil Development Company. S. L. Buacngs, W. K. McCoy, New England Fire Insurance Rating Gulf Oil Company. Association. W. H. Doym E. J. Mayan, Factory Insurance Association. Manufacturing Chemists Association. J. E HILL. H. E. NEWELL, Union Oil Company. National Board of Fire Underwriters. E. E. HOMMAN, Fa® A. TRASH, National Paint, Varnish and Lacquer OB Insurance Amociation. Association. W. S. MARSH, FRANK G. Wnsox, Factory Mutual Engineering Div. American Petroleum Institute. F. R. MCLgAx, W. N. YOUNG, socony-Vacuum OB Co. Shell Oil Company. NFPA COMMITTEE ON LAWS AND ORDINANCES. LEON A. WATSON, Chairman, The Fire Insurance Rating Organization of New Jersey, Newark. GwaGH W. CwuoH, F. T. Moses, NFPA Fire Marshals' Section. Firemen'a Mut. Inc. Co. Lawes A. VlxcaNT C. E. RIDLEy, National Board of Fire Underwriters. International City Managers Ame, FOREWORD. This, the 1951 edition of the NFPA Suggested Ordinance on Flammable Liquids adopted May 11, 1951, supersedes all previous editions. Drafted by the Conference Committee listed on page two, reviewed, amended and submitted to the Association by the Committee on Flammable Liquids, further amended in detail of legal form on the recommendation of the NFPA Committee on Laws and Ordinances, it represents the National Fire Protection Association's official recommendations for municipal regulation of the storage and handling of gasoline and other flammable liquids in the interest of public safety. It is only a recommendation as far as the NFPA is concerned, but like its successive predecessor editions dating back to the first edition issued December 1, 1913, is offered as a guide to reasonable municipal legislation. While drafted for adoption by a city, it can be used by states or other jurisdictions with appropriate changes in wording. In any case, the text should be checked by legal counsel for its suitability for any individual city ; the present text while drafted for general use, may require minor changes to meet special constitutional and legislative require- ments in some jurisdictions. The Fire Department is indicated as the enforcing agency in this text, which is consistent with the present practice in the majority of American cities. However, with minor changes in wording, it may be equally well used by the Building Department, Fire Marshal Department, or other regulatory agency. This ordinance makes reference to other standards for various matters which it is not practicable to cover in detail in this ordinance. A list of such references is printed on pages 46 and 47. To avoid legal criticism on the ground of improper delegation of legislative power, these references are to specifically identified editions, the latest current at the time of this NFPA printing. However, to keep up to date, this text should be amended periodically to make reference to the current editions of such reference standards, all of which are subject to amendment from time to time. It is highly desirable, where legally permissible, to make appropriate provision for automatic utilization of new editions of reference publications as issued. The NFPA office will at any time on request provide information on the current status of such reference standards. A full history of NFPA action on this and previous editions of the Flammable Liquids Ordinance will be found in the published NFPA Proceedings and Advance Reports for the various years. A condensed history will be found in the National Fire Codes, Vol. !, Flammable Liquids, Gases, Chemicals and Explosives, in which this ordinance also appears. The present 1951 edition is the result of intensive committee work over a period of several years, printing and circulation of several successive drafts, and full consideration of all suggestions received from every source. In addition to the committees listed, the NFPA is indebted to Mr. Charles S. Rhyne, General Council, National Institute of Municipal Law Officers, Washington, D. C., for his assistance in clarifying the legal terminology in several sections of this ordinance. 4 SUGGESTED ORDINANCE FOR THE STORAGE, HANDLING AND USE OF FLAMMABLE LIQUIDS. (No. 30-L) CHAPTER I. GENERAL PROVISIONS. 101. Title: This ordinance shall be known as "an ordinance regulating the storage, handling, and use of flammable liquids in the city and may be referred to as "The Flammable Liquids Ordinance."* 102. Application : This ordinance shall apply to all persons, firms, corpora- tions, copartnerships, governmental agencies except Federal, and voluntary associations storing, handling or using flammable liquids, and to the owner or lessee of any building, premises, or equipment in or on which flammable liquids are stored, handled, or used. 103. Scope: This ordinance shall apply to flammable liquids as hereinafter defined ; except that it shall not apply to the transportation of flammable liquids in bulk** or to transportation when in conformity with Interstate Commerce Commission regulations, or regulations lawfully on 'file with and approved by the Interstate Commerce Commission. 104. Definitions: 104.01 "AIRCRAFT SERVICE STATION shall mean that portion of an airport where flammable liquids used as aircraft fuel are stored or dispensed from fixed equipment and shall include all facilities essential thereto. 104.02 "APPROVED' signifies acceptance, by the chief, of design, equip- ment, installation, or intended use as required by this ordinance. 104.03 "AUTOMOTIVE SERVICE STATION" Shall mean that portion of a property where flammable liquids used as motor fuels are stored and dispensed from fixed equipment into the fuel tanks of motor vehicles. 104.04 'BARREL" shall mean a volume of 42 U. S. gallons. 104.05 "BULK PLANT" shall mean that portion of a property where flammable liquids are received by tank vessel, pipe lines, tank car, or tank vehicle, and are stored or blended in bulk for the purpose of distributing such liquids by tank vessel, pipe line, tank car, tank vehicle, or container. 104.06 "CHIEF" shall mean the chief of the fire department (or other authorized person or body) and shall include any officer, member, or inspector deputized for the purposes of this ordinance by the chief. •The title should conform with local law and practice. *•NFPA No. 886, Regulatory Standard for Tank Vehicles for Flammable Liquids (1848) available from National Fire Protection Association, 60 Batterymarck SL Boston 10, Maas. 5 6 FLAMMABLE LIQUIDS ORDINANCE o„tay a tcc�cci 0i 41 e," „C ( >� 104.07 "CITY COUNCIL" shall mean the Fire—Commission-,er-,other. d-o"= steer Board-of-Supervisors,-etc,). city VfFayette ✓r'I/e, 4.- , 104.08 "CLOSED CONTAINER" shall mean a container as herein defined, so sealed by means of a lid or other device that neither liquid nor vapor will escape from it at ordinary temperatures. 104.09 "COMMERCIAL OR INDUSTRIAL ESTABLISHMENT" shall mean a place wherein the storage, handling, or use of flammable liquids is incidental to but not the principal business or process. 104.10 "CONTAINER" shall mean any can, bucket, barrel, drum, or port- able tank, except stationary tanks, tank vehicles, and tank cars. 104.11 "CRUDE PETROLEUM" shall mean hydrocarbon mixtures that have a flash point below 150° F. and which have not been processed in a refinery. 104.12 "FLAMMABLE LIQUID" shall mean any liquid having a flash point below 200° F. and having a vapor pressure not exceeding 40 pounds per square inch (absolute). Flammable liquids shall be divided into three classes as follows : CLASS I shall include those having flash points at or below 20° F. CLASS II shall include those having flash points above 20° F. but at or below 70° F. CLASS III shall include those having flash points above 70° F. The volatility of flammable liquids is increased when artificially heated to temperatures equal to or higher than their flash points. When so heated Class II and III liquids shall be subject to the applicable requirements for Class I or II liquids. This ordinance may also be applied to high flash point liquids which otherwise would be outside of its scope when they are so heated. 104.13 "FLASH POINT' shall mean the minimum temperature in degrees Fahrenheit at which a flammable liquid will give off flammable vapor as determined by appropriate test procedure and apparatus as specified below.* The flash point of flammable liquids having a flash point below 175° F. (79° C.) shall be determined in accordance with the Standard Method of Test for Flash Point by Means of the Tag Closed Tester (A.S.T.M. D56-36) as published in the book of American Society for Testing Materials Stand- ards ( 1949) !• This method is also the Standard of the National Fire Pro- tection Association (National Fire Codes Vol. 1, 1948) ,1 the Standard of the American Petroleum Institute (A.P.I. No. 509-36) , and the Standard of the American Standards Association (ASA Z11.24-1936) . $This section should conform to local law and practice with respect to adoption by "reference" or where conformity with a published standard is deemed to be prima facie evidence of compliance with the ordinance. **Available from American Society for Testing Materials, 1916 Race St., Phila. 8, Pa. tAvailable from National Fire Protection Association, 60 Batterymarch St., Roston GENERAL PROVISIONS 7 The flash point of flammable liquids having a flash point of 700 F. or below shall be determined by the apparatus and procedure called for in Sections 7 and 8 of this A.S.T.M. Method D56-36. The flash point of flammable liquids having a flash point of 1750 F. or higher shall be determined in accordance with the Standard Method of Test for Flash Point by Means of the Pensky-Martens Closed Tester (A.S.T.M. D93-46) as published in the Book of American Society for Test- ing Materials Standards ( 1949) ! This method is also the Standard of the National Fire Protection Association (National Fire Codes Vol. I, 1948) !* that Standard of the American Petroleum Institute (A.P.I. No. 510-46) , the Standard of the American Association .State Highway Officials (A.A.S.H.O.T:73-46) , and Standard of the American Standards Association (ASA Z11.7-1947) . 104.14 "MARINE SERVICE STATION" shall mean that portion of a prop- erty where flammable liquids used as motor fuels are stored and dispensed from fixed equipment on shore, piers, wharves, or barges into the fuel tanks of floating craft, and shall include all facilities used in connection therewith. 104.15 "PROCESSING PLANT" shall mean that portion of a property in which flammable liquids are mixed, heated, separated or otherwise processed as principal business, but shall not include plants defined herein as refineries. 104.16 "REFINERY" shall mean a plant in which flammable liquids are produced on a commercial scale from crude petroleum, natural gasoline, or other hydrocarbon sources. 104.17 "SAFETY CAN" shall mean an approved container, of not over 5 gallons capacity, having a spring-closing lid and spout cover. 104.18 "VAPOR PRESSURE' shall mean the pressure, measured in pounds per square inch (absolute) exerted by a volatile liquid as determined by the Standard Method of Test for Vapor Pressure of Petroleum Products (Reid Method) ," (A.S.T.M.D. 323-49) as published in the Book of American Society for Testing Materials Standards ( 1949) ! This method is also the standard of the American Standards Association (A.S.A. Zll.44-1949) .1 105.[ Retroactivity : The chief shall issue a permit for the continued use of an existing plant, stare, equipment, building, structure, and installation for the storage, handling, or use of flammable liquids which is not in strict com- pliance with the terms of this ordinance in all cases in which such continued use will no[ constitute a distinct hazard to life or adjoining property. In all rases where such permit is denied the chief shall notify the applicant and specify the reasons for denial in writing. *Available from American Society for Testing Materials, 1916 Race St.. Phila. S. Pa. "Available from National Fire Protection Association, 60 Batterymarch St., Boston 10, Mass. tThis section should conform to local law and practice with respect to adoption by "reference" or where conformity with a published standard is deemed to be prima facie evidence of compliance with this ordinance. S FLAMMABLE LIQUIDS ORDINANCE 106. Permits: A permit issued pursuant to this ordinance shall be obtained from the Chief for any of the following : r . 106.01 Storage, handling, or use of Class I or Class II flammable liquids in excess of 1 gallon in a dwelling or other place of human habitation ; or in excess of 6 gallons in any other building or other occupancy ; or in excess of 10 gallons outside of any building ; except that no permit shall be required for the following : 106.01-1 For the storage or use of flammable liquids in the fuel tank of a motor vehicle, aircraft, motorboat, mobile power plant, or mobile heating plant. - 106.01-2 For the storage or use of paints, oils, varnishes, or similar flammable mixtures when such liquids are stored for maintenance, painting, or similar purposes for a period of not more than 30 days. 106.02 Storage, handling, or use of - Class III flammable liquids in excess of 25 gallons in a building ; or in excess of 60 gallons outside of a building. 106.03 For the manufacture, processing, blending, or refining of flam- mable liquids. 106.04 For the storage of flammable liquids in stationary tanks. 107. Inspection and Approval. 107.01 Application for a permit to construct or erect facilities for the storage, handling or use of flammable liquids as herein required shall be made in writing to the Chief. The Chief shall then muse to be made an inspection of the premises and equipment proposed to be used. If they are found to be in compliance with this ordinance, a statement to that effect shall be noted on the application and the application signed by the person making the inspection The Chief shall thereupon issue a permit as applied for. 107.02 Before operating any equipment or storing any flammable liquid, or covering the underground portions of any such equipment for which a permit is required, notification shall be given to the Chief and he shall, within two working days thereof, cause such premises or equipment to be inspected. 107.03 The Chief may at any reasonable time inspect premises, build- ings, installations, or equipment for the storage, handling, or use of flammable liquids. If a violation of this ordinance is found to exist, he shall file with the owner, occupant, or operator a notice citing the violation and ordering its correction. If such order is not complied with, the Chief may suspend the permit issued for such facility. 107.04 Containers, tanks, equipment and apparatus meeting the stand- ards of nationally recognized inspection or test laboratories shall be con- sidered as meeting the requirements of this section. CHAPTER II. STORAGE I CHAPTER II. STORAGE. Part OneStorageAboveground (Outside of Buildings). 201. Restricted Locations : The storage of , Class I and II flammable liquids in aboveground tanks outside of buildings is prohibited within the following limits : ( Note : These limits to be specified. They should include the mercantile and other congested districts.) 202. Location with Respect to Property Lines : Location of an above- ground tank for storage of flammable liquids with respect to distance from the nearest line of adjoining property which may be built upon, shall be such that the distance between any part of the tank and the line shall be not less than that set forth in the following : MINIMUM DISTANCE OF OUTSIDE ABOVEGROUND TANKS FOR FLAMMABLE LIQUIDS OTHER THAN CRUDE PETROLEUM To LINE OF ADJOINING PROPERTY WHICH MAY BE BUILT UPON. Class or Flammable Capacity of Tank Liquid Minimum Distaaw 0 to 275 gals. III 0 feet 276 to 750 gals. III 5 feet 0 to 750 gals. I and II 10 feet 751 to 12,000 gals. III 10 feet 751 to 12,000 gals. I and II 15 feet 12,001 to 24,000 gals. I, II, and 1II 15 feet 24,001 to 30,000 gals. I, II, and III 20 feet 30,001 to 50,000 gals. I, II, and III 25 feet Tanks with capacities in excess of 50,000 gallons and all tanks for storage of crude petroleum shall be located in accordance with the following provisions : GROUP A TANKS. Any all-steel, gas-tight tank constructed incom- pliance with these or equivalent standards and equipped either with ( 1 ) an approved permanently attached extinguishing system or (2) an approved floating roof, which is to be used only for the storage of refined petroleum products or other flammable liquids not subject to boil-over, shall be so located that the distance from the line of adjoining property which may be built upon shall be not less than the greatest dimension of diameter or height of the tank, except that such distance need not exceed 120 feet. GROUP B TANKS. Any all-steel, gas-tight tank constructed in com- pliance with these or equivalent standards but not equipped either with. ( 1 ) an approved permanently attached extinguishing system or (2) an approved floating roof, which is to be used only for the storage of refined petroleum products or other flammable liquids not subject to boil-over, shall be , so 10 FLAMMABLE LIQUIDS ORDINANCE located that the distance from the line of adjoining property which may be built upon shall be not less than 1% times the greatest dimension of diameter or height of the tank, except that such distance need not exceed 175 feet. GROUP C TANKS. Any all-steel, gas-tight tank constructed in com- pliance with these or equivalent standards and equipped either with ( 1) an approved permanently attached extinguishing system or (2) an approved floating roof, which is to be used for the storage of crude petroleum,* shall be so located that the distance from the line of adjoining property which may be built upon shall be not less than twice the greatest dimension of diameter or height of the tank except that such distance shall be not less than 20 feet and need not exceed 175 feet. GROUP D TANKS. Any all-steel, gas-tight tank constructed in com- pliance with these or equivalent standards and not equipped either with ( 1 ) an approved permanently attached extinguishing system or (2) an approved floating roof, which is to be used for the storage of crude petroleum,* shall be so located that the distance from the line of adjoining property which may be built upon shall be not less than three times the greatest dimension of diameter or height of the tank except that such distance shall not be less than 20 feet and need not exceed 350 feet. NOTE: The term "approved permanently attached extinguishing syste t" as used in the foregoing description may be interpreted to apply to a fixed foam or other recognized extinguishing system embodying a supply of the extinguishing medium, or a system employing a pipe line for conveying foam from a point outside the dike to the tank, subject to the approval of the enforcing authority. Where reliance is placed upon such a pipe for conveying foam, the pipe tine should be so installed and attached as to be an integral part of the tank. Approved portable foam generating equipment of sufficient capacity should be available on the property, by response of a municipal fire department or otherwise readily available, and there should be on hand or readily available a sufficient supply of foam-producing materials as specified in the NFPA Standards for Foom Extinguishing Systems." 202.01 In particular installations these provisions may be altered at the discretion of the Chief after consideration of the special features such as topographical conditions ; nature of occupancy and proximity to buildings on adjoining property and height and character of construction of such buildings ; capacity and construction of proposed tanks and character of liquids to be stored ; degree of private fire protection to be provided, and facilities of the fire department to cope with flammable liquid fires. 203. Spacing Between Tanks. 203.01 The location of a tank for the storage of any flammable liquid with respect to any such other tank shall be such that the distance between them shall be not less than 3 ft. 'Certain products. not petroleum products, handled in special proems and chemical plants may have boil-over characteristics somewhat like those of crude petroleum. "Standard No. 11 ( 1951 ) published in National Fire Codes Vol. IV and in separate Pamphlet form : available from National Fire Protection Association, 60 Battary- march St., Boston 10, Mass. CHAPTER H. STORAGE 11 203.02 For tanks above 50,000 gallons individual capacity storing any flammable liquid, except crude petroleum in producing areas, the distance shall be not less than one-half the diameter of the smaller tank. 203.03 For tanks storing crude petroleum above 126,000 gallons (3,000 bbls.) individual capacity, the distance shall be not less than the diam- eter of the smaller tank. 204. Foundations and Supports: Tanks shall rest directly on the ground or on foundations or supports of concrete, masonry, piling, or steel. Exposed piling or steel supports shall be protected by fire -resistive materials to provide a fire -resistance rating of not less than two hours. 204.01 ANCHORAGE: Where a tank is located in an area that may be subjected to flooding, the applicable precautions outlined in Appendix B shall be observed. 205. Stairs, Platforms and Walkways: Stairs, platforms and walkways shall be of steel, concrete, or wood. 206. Dikes and Walls. 206.01 CRUDE PETROLEUM: Tanks or groups of tanks containing crude petroleum* shall be diked or other suitable means taken to prevent discharge of liquid from endangering adjoining property or reaching waterways. Where a diked enclosure is required under this section, it shall have a capacity not less than that of the tank or tanks, provided, however, that a single diked enclosure shall not contain a group of tanks having a total capacity in excess of 170,000 barrels. 206.02 FLAMMABLE LIQUIDS OTHER THAN CRUDE PETROLEUM: Indi- vidual tanks or groups of tanks, where deemed necessary by the Chief on account of proximity to waterways, character of topography, or nearness to structures of high value, or to places of habitation or assembly, shall be diked or the yard shall be provided with a curb or other suitable means taken to prevent the spread of liquid onto other property or waterways. Where a diked enclosure is required under this section, it shall have a net capacity not less than that of the largest tank plus 10 per cent of the aggre- gate capacity of all other tanks served by the enclosure. 206.03 DIKE CONSTRUCTION: Except where protection is provided by natural topography, dikes or retaining walls required under the foregoing section shall be of earth, concrete or solid masonry designed to be liquid tight and to withstand a full hydraulic head, and so constructed as to provide the required protection. Earthen dikes 3 ft. or more in height shall have a flat section at the top not less than 2 ft. wide. The slope shall be consistent with the angle of repose of the material of which the dikes are constructed. Unless means are available for extinguishing a fire in any tank containing crude petroleum, dikes and walls enclosing such tanks shall be provided at the top with a flareback section designed to turn back a boil -over wave, provided, however, that a flareback section shall not be required for dikes and walls enclosing approved floating roof tanks. •Certain products, not Petroleum Products, handled in special process and chemical plants may have boil -over characteristics somewhat like those of crude petroleum. 12 FLAMMABLE LIOUIDS ORDINANCE 206.04 DRAINAGE: Where provision is made for draining rain water from diked areas, such drains shall normally be kept closed and shall be so designed that when in use, they will not permit flammable liquids to enter natural water courses, public sewers, or public drains, if their presence would constitute a hazard. 207. Design and Construction of Tanks Operating at Substantially Atmospheric Pressure: Tanks shall be built of steel or concrete unless character of liquid stored requires other materials. Steel commonly known as "Mill Seconds" shall not be used. Tanks built of materials other than steel or concrete shall be designed to specifications embodying safety factors equivalent to those herein specified for steel tanks. Concrete tanks built in accordance with "Standards for the Design and Construction of Concrete Fuel Oil Storage Tanks (1922)" adopted by the National Fire Protection Association and published in National Fire Codes, Vol. 1, (1948), shall be deemed prima facie evidence of compliance with this section and three copies of this standard shall be filed by the Chief with the city clerk and kept available for examination." Such (unlined) concrete tanks shall only be used for storage of liquids having a gravity of 400 A.P.I. or heavier. Con- crete tanks with special linings may be used for other services provided the design is approved by the Chief. Steel tanks shall be built in accordance with is approved by the Chief. Steel tanks shall be built in accordance with the the requirements of the following paragraphs. All shop -built tanks shall be tested at a pressure of not less than five and not more than ten pounds per square inch (measured at the top of the tank) for a period of at least ten minutes without leakage or permanent deformation. 207.01 FIELD ERECTED VERTICAL TANKS: Vertical tanks erected in the field and built in accordance with American Petroleum Institute Standard No. 12A, 7th Edition, March 1941, "Specification for Standard Tanks with Riveted Shells for Oil Storage," or American Petroleum Institute Standard No. 12C, 9th Edition, October 1950, "Specification for Welded Oil Storage Tanks,"t shall be deemed to comply with this section and three copies of this standard shall be filed by the Chief with the city clerk and kept available for examination.** 207.02 SMALL SHOP BUILT VERTICAL TANKS: Vertical tanks not over 1,100 gallons capacity shall meet the following standards: Minimum Thickness of steel Capacity (Gallons) U. S. Standard 1- 60 18 gauge 61- 350 16 gauge 351- 560 14 gauge 561 - 1,100 12 gauge 207.03 LARGE SHOP BUILT VERTICAL TANKS: Vertical tanks over 1,100 gallons capacity shall meet the following standards: 'Available from National Fire Protection Association, 60 Batterymarch St.. Boston 10, Mass. "This section should conform to local law and proctice with respect to adoption by "reference" or where conformity with a published standard is deemed to be prima facie evidence of compliance with this ordinance. Monies of these standards available from: American Petroleum Institute, 60 West 50th Street, New York 20, N. Y. CHAPTER II. STORAGE 13 - For tanks up to 25 ft. in height the shell shall be not less than 3/16 in. thick. For tanks from 25 to 30 ft. high the bottom ring shall be not less than '/y in. thick and the remainder of the shell not less than 3/16 in. thick. For tanks between 30 and 35 ft. high, the first two rings shall be not less than / in. thick and the remainder of the shell not less than 3/16 in. thick All / in. thick rings shall be not less than 5 ft. wide. The tops of tanks shall be either dished or cone -shaped and of not less than No. 10 U. S. Standard gauge steel. Tanks shall be welded, or riveted and caulked, or otherwise made tight in a workmanlike manner. The roof of the tank shall be securely fastened to the top ring of the shell with a joint having the same tightness as the joints between rings. The joint between roof and shell shall be weaker than any other joints in the shell of the tank. Joints in the roof shall be welded or riveted or made tight by other process satisfactory to the Chief. Roofs of tanks shall have no unprotected openings. NOTE: Tanks in this category which have been labeled by the Underwriters' Laboratories, Inc. may be considered as meeting the requirements of this section. 207.04 PRODUCTION TANKS: Vertical tanks not exceeding 126,000 gallons (3,000 bbls.) individual capacity,* when used for crude petroleum storage in oil producing areas, shall be deemed prima facie evidence of com- pliance with this section when built in accordance with American Petroleum Institute Standard No. 12B, 5th Edition, Sept. 1944, with Supplement No. 4, dated December 1949 —"Specification for Standard Bolted Tanks," and Stand- ard 12D, 3rd Edition, Sept. 1911 "Welded Production Tanks," and "Supplement No. 2, August 1947" thereto.** 207.05 SHOP BUILT HORIZONTAL TANKS: Horizontal tanks shall be constructed in accordance with accepted engineering practice and shall meet the following minimum requirements: Joints shall be riveted and caulked, riveted and welded, or welded. Tank heads over 6 ft. in diameter shall be dished, -stayed, braced, or reinforced. 207.05-1 SMALL SHOP BUILT HORIZONTAL TANKS: Horizontal tanks not over 1,100 gallons capacity shall meet the following standards: Capacity (Gallons) Minimum ti Thickness of Steel Standard 1 to 60 18 gauge 61 to 275 14 gauge 276 to 550 12 gauge 551 to 1,100 10 gauge 207.05-2 LARGE SHOP BUILT HORIZONTAL TANKS: Horizontal . tanks over 1,100 �l gallons �capacity having a diameter of not over 6 ft made of steel shall be t e in. or greater nominal thickness. Tanks having a diameter of over 6 ft. and not more than 12 ft., made of steel, shall be / in. or greater nominal thickness. *This section should conform to local law and practice with respect to adoption by reference" or where conformity with a published standard is deemed to be prima facie evidence of compliance with the ordinance. Copies of these standards available from American Petroleum. Institute, 60 West 60th Street, New York 20, N. Y. 14 FLAMMABLE LIQUIDS _ cE xx» x »»4 )-222���J�2�� § I-. | ( k � <$I' Z7/J.- ! /|/ - - - - `o! • ;., fl to ) !! §!" o. °` w |/$m,lv |\ \)!/ /Q 4@5§Rk$m§'0 ® as dd 2 o E - /f}!°`nmRmaa»m `�``\w»>\b t ` ||.zV06 o 4%} !` 2"2M5m;»a CHAPTER II. STORAGE Is NOTE: Tanks in this category which have been labeled by the Underwriters' Laboratories, Inc. may be considered as meeting the requirements of this section. 208. Vents. 208.01 VENTS FOR NORMAL BREATHING: Tanks shall have normal venting capacity sufficient to permit the filling and emptying of such tanks, plus their breathing due to temperature changes, without distortion of tank shell or roof. Tanks storing Class I and Class II flammable liquids shall be equipped where practical + with either venting devices which shall be nor- mally closed when not under pressure or vacuum, or with approved flame arresters,** except that tanks under 2,500 gallons capacity for Class I liquids and tanks under 3,000 barrels capacity for crude oil in producing areas may have open vents. 208.02 VENTS FOR EMERGENCY RELIEF: In addition to the provisions for normal venting herein required, every aboveground storage tank shall have some form of construction or device that will relieve excessive internal pressure, caused by exposure fires, that might cause the rupture of the tank shell or bottom. In a vertical tank, this construction may take the form of a weakened seam in the roof. The joint between the roof and the shell of a tank 36 ft. or more in diameter, if built in accordance with Section 207.01 of this ordinance, shall be deemed to be a weakened seam for this purpose. Where entire dependence for such additional relief is placed upon some device other than a weak roof seam or joint, the total venting capacity of both normal and emergency vents shall be enough to prevent rupture of the shell or bottom of the tank if vertical, or of the shell or heads if horizontal. Such device may be a self -closing manhole cover, or one using long bolts that permits the cover to lift under internal pressure, or an additional or larger relief valve or valves. For the purpose of computing the number and area of such vents and emergency relief devices, reference may be made to the table, Required Capacities for Emergency Relief (preceding page). 209. Tank Valves: Each connection to an aboveground tank storing flam- mable liquids, located below normal liquid level, shall be provided with an internal or external control valve located as close as practicable to the shell of the tank. Except for flammable liquids whose chemical characteristics are incompatible with steel, such valves, when external, and their connections to the tank shall be of steel. Part Two. Storage Underground or in Buildings. 210. Underground. 210.01 LOCATION CLASS I AND II: An underground tank for Class I or Class II flammable liquids shall be located not less than the distance indi- cated in the table below, measured horizontally from the nearest point of the shell to the nearest line of adjoining property that may be built upon and the nearest outside wall of any basement, pit, or cellar, of which the floor is •Condensation and crystallization of certain products and freezing in winter may make conservation vents and particularly flame arresters impractical for these products and for use In very cold weather. ••Where the liquids stored have flesh points in the range of normal summer tempera- tures. the vapor space above the liquid In the tank will normally contain vapors in the explosive range. On such tanks flame arresters have their most important application. FLAMMABLE LIQUIDS ORDINANCE lower in elevation than the top of such tank. Where such location causes unnecessary hardship, an underground tank may be placed closer than the distance specified if enclosed, encased or otherwise protected from physical damage. MINIMUM DISTANCE FROM UNDERGROUND TANKS FOR CLASS I OR II FLAMMABLE LIQUIDS TO BASEMENTS OR TO LINE OF ADJOINING PROPERTY THAT MAY BE BUILT UPON. Location It too of tank is above the lowest Individual Tank Capacity floor, basement, cellar or part of Class I and If any building which is not less than: 550 Gallons 5 feet away 5,000 gallons 10 feet away 10,000 gallons 15 feet away 15,000 gallons 20 feet away Unlimited 25 feet away 210.02 DEPTH AND COVER: Underground tanks shall be set on firm foundation and surrounded with soft earth or sand well -tamped in place. Tanks shall be covered with a minimum of 2 ft. of earth, or shall be covered with not less than one foot of earth on top of which shall be placed a slab of reinforced concrete not less than four (4) inches thick. When subjected to traffic, tanks shall be protected against damage from vehicles passing over them by at least 3 ft. of earth cover, or 18 inches of well -tamped earth, plus either 8 inches of asphaltic concrete or 6 inches of reinforced concrete. When asphaltic or reinforced concrete paving is used as part of the -protection it must extend at least 1 ft. horizontally beyond the outline of the tank in all directions. 210.03 ANCHORAGE: Where a tank may become buoyant due to a rise in the level of the water table or due to location in an area that may be subjected to flooding, the applicable precautions outlined in Appendix B shall be observed to anchor the tank in place. 211. Inside of Buildings, Class I or II: Tanks for storage of Class I and II flammable liquids shall not be installed inside buildings except as pro- vided under Chapters V and VII. Tanks for storage of Class I and II flam- mable liquids may be installed under a building as an underground tank complying with Section 210. 212. Inside of Buildings, Class III: Unenclosed tanks shall not be located within 5 ft., horizontally, of any fire or flame. Tanks larger than 60 gallons capacity shall not be located in buildings above the lowest story, cellar or basement, except in commercial, industrial or process plants where storage on a higher floor is required by the process. Tanks exceeding 275 gallons indi- vidual capacity or 550 gallons aggregate capacity in an individual building or in a section of a building separated by firewalls shall be installed in an enclosure constructed as follows: The walls of the enclosure shall be con- structed of reinforced concrete at least 6 in. thick or of brick at least 8 in. thick. Such enclosures shall be installed only on concrete or other fire - resistive floors and shall be bonded to the floors. Enclosures shall have tops of reinforced concrete at least 5 in. thick or equivalent fire -resistive con- struction, except that where floor or roof construction above the enclosure is concrete or other fire -resistive construction, the walls may be extended to and bonded to the underside of the construction above in lieu of the provision II. STORAGE 17 of a separate top. Any openings to such enclosures shall be provided with fire doors or other approved closures and six-inch noncombustible liquid tight sills or ramps. Provision shall be made for adequate ventilation of such enclosures prior to entering for inspection or repairs to tanks. In buildings of ordinary construction, the nominal gross capacity of tanks shall not exceed 5,000 gallons. In fire -resistive buildings the nominal gross capacity of the tanks shall not exceed 15,000 gallons. In any building, if in a fire -resistive or detached room cut off vertically and horizontally in an approved manner from other floors of the main building, the nominal gross capacity of tanks shall not exceed 50,000 gallons, with an individual tank capacity not exceeding 25,000 gallons. 213. Design and Construction of Tanks. 213.01 UNDERGROUND TANKS OR ENCLOSED TANKS INSIDE OF BUILD- INGS: Tanks shall be designed and constructed to withstand safely the service to which subjected. Material other than steel, if used, shall be of suitable durability and of thicknesses providing equivalent strength to that provided by steel. Steel commonly known as "mill seconds" shall not be used. Steel tanks shall be of a minimum gauge (U. S. Standard) in accordance with the following table: Minimum Nominal Thickness of Materiel U. S. Standard Pounds per Capacity (Gallons) Gauge Square Foot I to 285 No. 14 3.125 286 to 560 No. 12 4.375 561 to 1,100 No. 10 5.625 1,101 to 4,000 No. 7 7.50 4,001 to 12,000 / in. 10.00 12,001 to 20,000 I°s in. 12.50 20,001 to 30,000 34 in. 15.00 If adequate internal bracing is provided, tanks of 12,001 to 30,000 gallons capacity may be built of / in. plate. 213.02 UNENCLOSED TANKS INSIDE OF BUILDINGS: Tanks of this category used for Class III flammable liquids shall not exceed 275 gallons individual capacity. They may be cylindrical or of a special form which has been demonstrated by appropriate tests to possess strength and tightness of an acceptable degree. Material other than steel, if used, shall be of suitable durability and thickness to provide strength equivalent to that provided by steel. Steel commonly known as "mill seconds" shall not be used. Steel tanks shall be of a minimum gauge (U. S. Standard) in accordance with the following table: Minimum Nominal Thickness of Material U. S. Standard Founds per Capacity (Gallons) Gauge Square Foot 1 to 180 No. 16 2.50 181 to 275 No. 14 3.125 NOTE: Tanks in this category which have been labeled by the Underwriters' Laboratories, Inc., may be considered as meeting the requirements of this section. 18 FLAMMABLE LIQUIDS ORDINANCE 214. Support of Tanks in Buildings: Inside storage tanks shall be securely supported to prevent settling, sliding, or lifting. 215. Tank Connections for Tanks Underground or in Buildings. 215.01 VENTS. 215.01-1 LOCATION AND ARRANGEMENT OF VENTS -CLASS I OR II: Vent pipes from tanks storing Class I or Class II flammable liquids shall be so located that the discharge point is outside of buildings, higher than the fill pipe opening, and not less than 12 ft. above the adjacent ground level. Vent pipes shall discharge only upward or horizontally (not downward) in order to disperse vapors. Vent pipes 2 in. or less in nominal inside diameter shall not be obstructed by devices that will reduce their capacity and thus cause excessive back pressure. Vent pipe outlets shall be so located that flammable vapors will not enter building openings, or be trapped under eaves or other obstructions. If the vent pipe is less than 10 ft. in length or greater than 2 in. in nominal inside diameter, the outlet shall be provided with a vacuum and pressure relief device or there shall be an approved flame arrester located in the vent line at the outlet or within the approved distance from the outlet. In no case shall a flame arrester be located more than 15 feet from the outlet end of the vent line. 215.01-2 LOCATION AND ARRANGEMENT OF VENTS —CLASS III: Vent pipes from tanks storing Class III flammable liquids shall terminate outside of building and higher than the fill pipe opening. Vent outlets shall be above normal snow level. They may be fitted with return bends, coarse screens or other devices to minimize ingress of foreign material. 215.01-3 SIZE OF VENTS: Each tank shall be vented through piping adequate in size to prevent blow -back of vapor or liquid at the fill opening while tank is being filled. Vent pipes shall be not less than 1% in. nominal inside diameter. 215.01-4 VENT PIPING: Vent pipes shall be so laid as to drain toward the tank without sags or traps in which liquid can collect. They shall be located so that they will not be subjected to physical damage above ground. Vent pipes from tanks storing the same class of flammable liquids may be connected into one outlet pipe. The outlet pipe shall at least be one pipe -size larger than the largest individual vent pipe connected thereto. In no case shall the point of connection between vent lines be lower than the top of any fill -pipe opening. The lower end of a vent pipe shall enter the tank through the top and shall not extend into the tank more than 1 inch. 215.02 FILL AND DISCHARGE PIPING: Filling and discharge lines far Class I and Class II liquids, and for Class III liquids where practicable, shall enter tanks only through the top and shall be graded toward the tank. 215.03 FILL OPENINGS: The fill pipe opening shall be located outside of any building. For Class I or II flammable liquid storage the fill pipe opening shall be not less than 5 feet from any door or cellar opening. For Class III flammable liquid storage the fill pipe opening shall be not less than 2 feet from any building opening at the same or lower level. The fill -pipe opening shall be closed and liquid tight when not in use. Fill -pipe for filling by. tank car or tank truck shall be not larger than 4 in. nominal inside diameter and shall not be constricted. Fill -pipe openings shall be identified by a definite color scheme or other means. CHAPTER III. PIPING, VALVES, AND FITTINGS 19 215.04 GAUGE OPENINGS: Gauge openings, if independent of fill -pipe, shall be provided with liquid -tight cap or cover. Where Class I or Class II liquids are stored within a building, such gauge opening shall be protected against vapor release or liquid overflow by means of a spring -loaded check valve or other approved device. 215.05 DRAINAGE of TANKS IN BUILDINGS: Inside storage tanks for Class III flammable liquids shall be provided with draw -off or drain openings. Tanks shall be installed so that the bottom pitches to the draw -off or drain openings at a slope of not less than / in. per foot of length. The draw -off or drain opening shall be provided with suitable connection to provide a sump from which water or sediment can be drained readily. 216. Testing: Before being covered or placed in use, tanks and piping connected thereto must pass a test for tightness. Where the vent outlet is not more than 15 feet above the top of the tank the test pressure shall be at least 5 psi and either air or hydrostatic pressure may be used. Where the vent outlet is more than 15 feet above the top of the tank the test shall be made under hydrostatic pressure with the vent line flooded. In special cases where the height of the vent above the top of the tank is excessive the hydro- static test pressure shall be specified by the Chief. CHAPTER III. PIPING, VALVES, AND FITTINGS. 301. Materials and Design: Piping, valves, and fittings for flammable liquids shall be designed for the working pressures and structural stresses to which they may be subjected. They may be of steel or other materials suitable for use with the liquid being handled. Pipe -wall thicknesses determined by reference to "American Standard Code for Pressure Piping (A.S.A. 831.1, Edition of 1942, with Supplements B31 -la, November 1944, and B31 -lb, April 1947)" shall be deemed prima facie evidence of compliance with this section; provided, however, that light -wall piping under Schedule 40 of that code shall be permitted when complying with other provisions of the code!' All threaded joints and connections shall be made up with a suitable piping compound. 302. Protection Against Corrosion: All piping for flammable liquids, both aboveground and underground, where subject to external corrosion, shall be painted or otherwise protected. 303. Supports: Pipe systems shall be substantially supported and protected against physical damage and excessive stresses arising from settlement, vibra- tion, expansion or contraction. •Available from the American Society of Mechanical Engineers. 29 West 89th St., New York 18, N. Y. These provisions shall apply to all piping for flammable liquids which falls within the scope of this ordinance, even though the code of reference data not refer specifically to each type of installation. •'This section should conform to local law and practice with respect to adoption by "reference" or where conformity with a published standard is deemed to be prima facie evidence of compliance with the ordinance. 20 FLAMMABLE LIQUIDS ORDINANCE 304. Valves: Pipe systems shall contain a sufficient number of valves to operate the system properly and to protect the plant. Pipe systems in con- nection with pumps shall contain a sufficient number of valves properly to control the flow of liquid in normal operation and in the event of physical damage. Connections to pipe lines, by which equipment such as tank cars or tank trucks discharge flammable liquids by means of centrifugal pumps into aboveground storage tanks, shall be provided with check valves for automatic protection against back -flow. CHAPTER IV. BULK PLANTS. 401. Location of Plants: No new bulk plant shall be constructed within the portion of the city hereinafter described. (These limits to be defined as comprising such areas as those zoned solely for residential occupancies, and for mercantile establishments predominantly retail in character.) 402. Storage. 402.01 STORAGE -CLASS I OR II: Class I and Class II flammable liquids shall be stored in closed containers, or in storage tanks aboveground outside of buildings, or underground. (See Chapter II of this ordinance.) 402.02 STORAGE -CLASS III: Class III flammable liquids shall be stored in containers, or in tanks within buildings or aboveground outside of buildings, or underground. (See Chapter II of this ordinance.) 402.03 STORAGE OF CONTAINERS: Containers of flammable liquids when piled one upon the other shall be separated by dunnage, sufficient to provide stability and to prevent excessive stress on container walls. The height of piles shall be consistent with stability and strength of containers. 403. Filling and Emptying Containers: Containers of Class I or Class II flammable liquids shall not be drawn from or filled within buildings unless provision is made to prevent the accumulation of flammable vapors in hazardous concentrations. 404. Ventilation: Ventilation shall be provided for all rooms, buildings, or enclosures in which Class I or Class II flammable liquids are pumped or dispensed. Design of ventilation systems shall take into account the relatively high specific gravity of the vapors. Ventilation may be provided by adequate openings in outside walls at floor level unobstructed except by louvers or coarse screens. Where natural ventilation is impracticable, mechanical ven- tilation shall be provided. Mechanical systems, for removing flammable vapors, designed, installed and operated in accordance with National Fire Protection Association standards for the "Installation of Blower and Exhaust Systems" published in National Fire Codes, Vol. III, 1951, shall be deemed prima facie evidence of compliance with this section and three copies of this standard shall be filed with the city clerk by the Chief and kept available for examination.** 'Printed separately as pamphlet No. 91. Available from National Fire Protection Association, 60 Batterymarch St., Boston 10, Meas.; also available from National Board of Fire Underwriters, 85 John St., New York 38, N. Y. (Pamphlet No. 91). ••This section should conform to local law and practice with respect to adoption by "reference" or where conformity with a published standard is deemed to be prima facie evidence of compliance with this ordinance. CHAPTER IV. BULK PLANTS 405. Buildings. 405.01 GENERAL CONSTRUCTION: Buildings shall be constructed so that rooms in which flammable liquids are handled or stored, comply with the requirements of the zone or area in which located. Class I and Class II flammable liquids shall not be stored or handled within a building having a basement or pit into which flammable vapors may travel, unless such area is provided with ventilation designed to prevent the accumulation of flammable vapors therein. 405.02 EXITS: Rooms storing flammable liquids or in which flammable liquids are handled by pumps shall have exit facilities arranged to prevent occupants being trapped in the event of fire.* 405.03 HEATING: Rooms in which Class I or Class II flammable liquids are stored or handled shall be heated only by means not constituting a source of ignition, such as steam or hot water. Rooms containing heating appliances involving sources of ignition shall be located and arranged to prevent entry of flammable vapors. 406. Loading and Unloading Facilities. 406.01 TRUCK LOADING RACKS. 406.01-1 LOCATION: Truck loading racks dispensing Class I or Class II flammable liquids shall be separated from tanks, warehouses, other plant buildings, and nearest line of property that may be built upon by a clear distance of not less than 25 ft., measured from the nearest position of any fill stem. Buildings for pumps or for shelter of loading personnel may be part of the loading rack. 406.01-2 STATIC PROTECnoN: The following types of truck loading racks shall be equipped with protection against static sparks during truck filling: —racks dispensing Class I or Class II flammable liquids into open domes of tank trucks, and racks dispensing Class III flammable liquids into open domes of tank trucks which may contain flammable vapors from previous cargoes of Class I or Class II flammable liquids. Protection shall consist of a bare metallic bond -wire permanently electrically connected to the fill -stem or some part of the fill -stem piping. The free end of such wire shall be provided with a clamp or similar device for convenient attachment to some metallic part of the cargo tank of the tank truck. The bond -wire connection shall be made prior to opening the dome covers. It shall be maintained in place during the entire filling operation and the dome covers shall be securely dosed before the bond -wire is disconnected from the cargo tank. 406.01-3 DRAG CHAINS: Drag chains or similar devices on tank. trucks shall not be deemed to meet the requirements of the preceding paragraph for static protection. NOTE: The term "tank truck" or "truck" is intended to cover all types of vehicles used for the bulk transportation of flammable liquids on highways. It specifically includes tank full -trailers and tank semi -trailers as well as conventional tank trucks. 406.02 TANK CAR RACKS: Class I and Class II flammable liquids shall not be discharged from or loaded into tank cars unless protection against *See NFPA Building Exits Code, 1951. 22 FLAMMABLE LIQUIDS ORDINANCE stray currents has been provided and is used. Protection designed and installed in accordance with Circulars of the Association of American Rail- roads, No. 17-D, dated August 1, 1947,* and No. 17-E, dated August 1, 1947* shall be deemed prima facie evidence of compliance with this section and three copies of each circular shall be filed with the city clerk by the Chief and kept available for examination.** 406.03 CONTAINER FILLING FACILITIES: Class I and Class II flam- mable liquids shall not be run into containers unless the nozzle and container are electrically interconnected. Where the metallic floorplate on which the container stands while filling is electrically connected to the fill stem or where the fill stem is bonded to the container during filling operations by means of a bond -wire, the provisions of this section shall be deemed to have been complied with. 406.04 DRAINS: Provision shall be made to prevent flammable liquids which may be spilled at loading or unloading points from entering public sewers and drainage systems, or natural waterways. Connections to such sewers, drains, or waterways by which flammable liquids might enter shall be provided with separator boxes or other approved means whereby such entry is precluded. 407. Electrical Equipment: All wiring and electrical equipment including motors and electrical switch gear for pumps handling Class I or Class II flammable liquids shall be designed and installed so as to not create an ignition hazard. Electrical equipment designed and installed in accordance with the Standards known as the "National Electrical Code" (1951), as published by the National Fire Protection Association] shall be deemed to be in com- pliance with this section. 408. Sources of Ignition: Class I or Class II flammable liquids shall not be handled, drawn, or dispensed where flammable vapors may reach a source of ignition. Smoking shall be prohibited except in designated localities. "NO SMOKING" signs shall be conspicuously posted where hazard from flammable liquids vapors is normally present. 409. Fire Control: Suitable first -aid fire -control devices, such as small hose or portable extinguishers, shall be available to locations where fires are likely to occur. Additional fire -control equipment may be required where a tank of more than 50,000 gallons individual capacity contains Class I or Class II flammable liquids and where an unusual exposure hazard exists from surrounding property. Such additional fire -control equipment shall be suffi- cient to extinguish a fire in the largest tank. The design and amount of such equipment shall be in accordance with approved engineering standards. NOTE: This ordinance does not cover the design or operation of petroleum wharves, found in bulk terminals (shore). A guide to regula- tion of petroleum wharves was published in 1938 by NFPA under the title "Suggested Ordinance for Petroleum Wharves" and may be consulted for applicable sections. OAvailable from the Association of American Railroads, 69 East Van Buren St., Chicago. Ill. **This section should conform to local law and practice with respect to adoption by "reference" or where conformity with a published standard is deemed to be prima facie evidence of compliance with the ordinance. tNational Fire Codes, Volume V or as pamphlet No. 70; also available from the National Board of Fire Underwriters, 85 John St., New York 38, N. Y. (Pamphlet No. 70). CHAPTER V. SERVICE STATIONS 23 CHAPTER V. SERVICE STATIONS. 501. Location: Apparatus dispensing Class I flammable liquids into the fuel tanks of motor vehicles of the public shall not be located at a bulk plant unless separated by a fence or similar barrier from the area in which bulk - operations are conducted. 501.01 GENERAL CONSTRUCTION: Buildings shall be constructed so that rooms in which flammable liquids are handled or stored comply with the requirements of the zone or area in which located. Class I and Class II flammable liquids shall not be stored or handled within a building having a basement or pit into which flammable vapors may travel, unless such area is provided with ventilation designed to prevent the accumulation of flam- mable vapors therein. 502. Storage and Handling 502.01 GENERAL PROVISIONS: Class I and Class II flammable liquids shall be stored in closed containers, or in tanks located underground or in special enclosures as described in section 502.02. Class III flammable liquids shall be stored in containers or in tanks located underground or in special enclosures as described in section 502.02. Aboveground tanks, located in an adjoining bulk plant, may be connected by piping to service station under- ground tanks if, in addition to valves at aboveground tanks, a valve is also installed within control of service station personnel. 502.02 SPECIAL ENCLOSURES: When installation of tanks in accord- ance with section 210 is impractical because of property or building limita- tions, tanks for flammable liquids may be installed in buildings if enclosed as follows: Enclosure shall be substantially liquid and vapor tight without backfill. Sides, top and bottom of the enclosure shall be of reinforced con- crete at least 6 inches thick, with openings for inspection through the top only. Tank connections shall be so piped or closed that neither vapors nor liquid can escape into the enclosed space. Means shall be provided whereby portable equipment may be employed to discharge to the outside any vapors which might accumulate should leakage occur. 502.03 STORAGE INSIDE BUILDINGS: No Class I flammable liquids shall be stored or handled Within any service station building except packaged items, for example: cleaning fluid received and resold in unbroken metallic containers of not over one (1) gallon capacity each, or in approved non- metallic containers of not more than one quart capacity each. Class II flammable liquids in closed containers may be stored inside the station building. A container equipped with an approved pump shall be considered a closed container for purposes of storage only. No Class I or Class II flammable liquids shall be dispensed, or transferred from one container to another, inside of a service station building, provided, however, that flammable anti -freeze liquids may be dispensed in rooms of a service station building provided such rooms have approved heating devices and provided also that there is no open flame in such room lower than 8 ft. above floor level. Class III liquids may be stored and dispensed inside service station buildings from approved containers of not more than 120 gallons capacity each. 24 FLAMMABLE LIQUIDS ORDINANCE 502.04 LABELING: No sale or purchase of any Class I, II or III flammable liquids shall be made in containers unless such containers are clearly marked with the name of the product contained therein. 503. Dispensing Devices. 503.01 DESIGN AND CONSTRUCTION: Class I and Class II flammable liquids shall be transferred from underground tanks by means of fixed pumps so designed and equipped as to allow control of the flow and to prevent leakage or accidental discharge. Supplemental means shall be provided outside of the dispensing device whereby the source of power may be readily disconnected in the event of fire or other accident. Dispensing devices for Class I or Class II flammable liquids shall be of approved type. Devices meeting the standards of the Underwriters' Laboratories, Inc., shall be deemed to be in compliance with this section. Class I or Class II flammable liquids shall not be dispensed by pressure or gravity from drums, barrels, and similar containers. Gear pumps or similar positive displacement devices taking suction through the top of the container shall be used. Class I and Class II flammable liquids shall not be dispensed by a device that operates through pressure within a storage tank, unless the tank has been approved as a pressure vessel for the use to which it is subjected. In no case shall air or gas pressure be used for this purpose. 503.02 AUTOMATIC DISPENSING DEVICES: The dispensing of Class I flammable liquids into the fuel tank of a vehicle or container shall at all times be under the manual control of a competent person. The use of any device which permits the dispensing of Class I flammable liquids, when the hand of the operator of the discharge nozzle is removed from the nozzle control lever, is hereby forbidden. The installation and use of coin -operated dis- pensing devices for Class I flammable liquids is prohibited. 503.03 LocATroN: Dispensing devices at automotive service stations shall be so located that all parts of the vehicle being served will be on private property. 503.04 INSIDE GARAGES: Where an outside location is impractical, dispensing devices approved for inside use may be installed inside garage or similar establishment storing, parking, servicing or repairing automotive equipment upon the approval of the location and safeguards and issuance of permit therefor by the Chief. The dispensing device shall be located in an area of fire -resistive construction well away from vehicle storage and repair areas and well ventilated, preferably near a doorway. It shall be protected against physical damage by vehicles by mounting on a concrete island or by equivalent means and shall be located in a position where it cannot be struck by a vehicle descending a ramp or other slope out of control. A convenient remote emergency shut-off for electric power to the dispensing unit and the pump supplying it shall be provided. 504. Marine Service Station. 504.01 Pumps supplying flammable liquids at marine service stations shall be located on shore, or on a pier of solid -fill type, where practicable. 504.02 Class I and Class II flammable liquids shall not be dispensed into the fuel tanks of marine craft except by means of a hose, equipped with CHAPTER VI. COMMERCIAL AND INDUSTRIAL ESTABLISHMENTS 25 a self -closing nozzle and with a valve which must be held open by manual control while making a delivery. 504.03 Pipe lines at marine service stations, where attached to piers, wharves, or other structures, shall be protected against physical damage. A valve shall be provided in each line at or near the approach to the pier, wharf, or other structure whereby supply from shore may be shut off. 504.04 Class III flammable liquids may be dispensed into the fuel tanks of marine craft from tank trucks by gravity or power -operated pumps through a hose equipped with a self -closing nozzle. 505. Drainage: Provision shall be made in the area where Class I flam- mable liquids may be spilled to prevent liquids from flowing into interior of service -station buildings. Such provision may be by grading driveway, raising door sills, or other equally effective means. Crankcase drainings and flammable liquids shall not be dumped into sewers. 506. Safety Rules: There shall be no smoking on the driveway of service stations in the areas used for fueling motor vehicles, dispensing flammable anti -freeze or the receipt of products by tank truck, or in those portions of the building used for servicing automobiles, tractors or internal combustion engines. Conspicuous signs prohibiting smoking shall be posted within sight of the customer being served. Letters on such signs shall be not less than 4 in. high. The motors of all vehicles being fueled shall be shut off during the fueling operation. 507. First -aid Fire Appliances: Suitable first -aid fire -control devices, such as small hose or portable extinguishers, shall be available to locations where fires are likely to occur. CHAPTER VI. COMMERCIAL AND INDUSTRIAL ESTABLISHMENTS. 601. Manner of Storage. 601.01 Class I and Class II flammable liquids shall be stored only in aboveground tanks out of doors, in underground tanks, or in closed containers outside of buildings or in rooms of buildings meeting the requirements of "Type A Inside Storage or Mixing Rooms" (see Appendix A). Such room shall not contain more than 275 gallons nor more than a day's supply of these liquids. Storage outside of such room shall not exceed 25 gallons aggregate capacity and shall be in original sealed containers or in approved safety cans of not more than 5 gallons capacity. Distance from outside aboveground tanks to important buildings shall be not less than distance to property lines specified in the table under paragraph 202. 601.02 Class III flammable liquids may be stored in aboveground tanks out of doors or within buildings, in underground tanks, or in tanks in enclo- sures, or in containers out of doors or within buildings. Installation of a tank in an enclosure or casing shall be in accordance with the requirements and capacities outlined in paragraph 212. Distance from outside aboveground tanks to buildings shall be not less than distance to property lines specified in the table under paragraph 202. 26 FLAMMABLE LIQUIDS ORDINANCE 601.03 Containers of flammable liquids stored outdoors shall be segre- gated by an open space of at least 10 feet from roadways, sidewalks and structures so as not to constitute an immediate life or property hazard in event of fire. Special attention should be given to routes of egress for building occupants, window and door openings, and combustible exterior walls, platforms, cornices, and roofs in securing the desired separation. Containers piled one upon the other shall be separated by dunnage sufficient to provide stability and to prevent excessive stress on container walls. The height of piles shall be consistent with stability. Drums and barrels stored on their sides shall have their heads facing aisles so that leakage of bungs may be detected. Containers storing flammable liquids shall have caps, plugs, or bungs replaced immediately after use and when the container is empty. 602. Use of Flammable Liquids. 602.01 Class I or Class II flammable liquids in quantities requiring a permit shall be used only in buildings or separate rooms of buildings so located or designed to prevent the spread of fire to other structures or property or to other sections of the building. This shall be accomplished by confining the use of such liquids as follows: (1) to a detached one-story building; (2) to a one-story section cut off from the remainder of the building by an approved fire wall with any openings in this wall protected properly by approved automatic fire doors; (3) to a separate area within a fire -resistive building. The separating walls in the fire -resistive building shall have a fire resistance of not less than one hour with all openings in such walls protected by approved fire doors. Openings in fire walls or separating walls should have noncombustible, liquid -tight, raised sills or ramps at least six inches in height. 602.02 Installations made according to the Standards of the National Fire Protection Association on "Safeguarding Dry Cleaning and Dry Dyeing Plants" (1944)*; on "Dip Tanks Containing Flammable Liquids, Including Hardening and Tempering Tanks and Flow Coat Work" (1946)**; on "Spray Finishing Using Flammable Materials" (1950),t shall be deemed prima facie evidence of compliance with this section and three copies of each standard shall be filed with the city clerk by the Chief and kept available for examination.} j 603. Dispensing. 603.01 Class I or Class II flammable liquids shall not be drawn from or dispensed into vessels or containers within a building except by means of a device drawing from top of the tank or the container. Gravity discharge *National Fire Codes, Volume I (1948) available from National Fire Protection Association, 60 Batterymarch St., Boston 10, Mass.; also available from the National Board of Fire Underwriters, 85 John St., New York 38, N. Y. (Pamphlet No. 32). **National Fire Codes, Volume I (1948) ; also published by the National Board of Fire Underwriters (Pamphlet No. 34). tPmmphlet No. 33, available from National Fire Protection Association; also avail- able from the National Board of Fire Underwriters (Pamphlet No. 33). ttThis section should conform to local law and practice with respect to adoption by "reference" or where conformity with a published standard is deemed to be prima facie evidence of compliance with the ordinance. CHAPTER VI. COMMERCIAL AND INDUSTRIAL ESTABLISHMENTS 27 within a building of Class I or Class II flammable liquids from tanks, drums, or containers other than safety cans, is specifically forbidden, except where the nature of the manufacturing process requires gravity flow. Upon approval of the Chief, such gravity flow shall be permitted only from vessels storing flammable liquids sufficient for not more than one day's operation. 603.02 Class I or Class II flammable liquids shall not be dispensed within a room or building which normally contains sources of ignition, within the possible path of vapor travel. Dispensing devices shall be provided with iron or steel valves where compatible with the flammable liquid handled. Where practicable, there shall be, in addition to the outlet valve, a secondary control device or valve outside of the immediate area, by which the flow may be stopped in the event of fire or other accident at the outlet. Outlet valves, where practicable, shall be of the self -closing type. 603.03 CONTAINER FILLING FACILITIES: Class I and II flammable liquids shall not be run into containers unless the nozzle and container are electrically interconnected. Where the metallic floor plate on which the con- tainer stands while filling is electrically connected to the fill stem or where the fill stem is bonded to the container during filling operations by means of a bond -wire, the provisions of this section shall be deemed to have been complied with. 603.04 ExITs: Buildings or rooms in which flammable liquids are stored or handled shall have exit facilities arranged to prevent occupants being trapped in the event of fire.* 604. Ventilation. . 604.01 Buildings, or rooms or other enclosures in which Class I or Class II flammable liquids are used or stored in open vats or dip tanks shall be provided with ventilation sufficient at all times to prevent accumulation of flammable vapors. Where natural ventilation is insufficient under all condi- tions to prevent the accumulation of flammable vapors, mechanical ventilation shall be provided and used. The accumulation of flammable vapors within the combustible or explosive range under normal operating conditions, as determined by an approved flammable -vapor indicator, shall be prima facie evidence of the violation of this section. 604.02 Design of ventilating systems shall take into account the rela- tively high specific gravity of the vapors. Openings to the outside for natural ventilation shall be at floor level and shall be unobstructed except by louvers, or coarse screens. Mechanical systems for removing flammable vapors, designed, installed and operated in accordance with National Fire Protection Association Standards for the "Installation of Blower and Exhaust Sys- tems," published in National Fire Codes, Vol. III, 1951!* shall be deemed prima facie evidence of compliance with this section and three copies of this *See National Fire Protection Association Building Exits Code, National Fire Codes, Vol. III, 1951. "National Fire Codes, Vol. III (1951) available from National Fire Protection Asso- ciation; also available from the National Board of Fire Underwriters, 85 John St. New York 38, N.Y. (Pamphlet No. 91). 28 FLAMMABLE LIQUIDS ORDINANCE standard shall be filed with the city clerk by the Chief and kept available for examination* 605. Sources of Ignition: Open flames, heating devices and processes employing temperatures capable of igniting the vapors of the flammable liquids used shall be prohibited in buildings, rooms and other confined spaces in which Class I or Class II flammable liquids are used in the open, or in which Class III flammable liquids are used for the purpose of saturating, coating or otherwise treating goods or materials. Artificial lighting shall be by electricity only. Electric devices located within the possible path of vapor travel shall be of a type approved for such locations. Compliance with applicable provisions of the "National Electrical Code" (1951) as published by the National Fire Protection Association** shall be deemed prima facie evidence of compliance with this section and three copies of this standard shall be filed with the city clerk by the Chief and kept available for examina- tion.* Smoking shall be prohibited and suitable signs to that effect shall be displayed. 606. Housekeeping. 606.01 Wherever flammable liquids are stored in containers, provision shall be made and maintained for the detection of leakage. Leaking containers shall be immediately removed or made tight. 606.02 Access shall be provided by unobstructed aisles whereby first - aid fire -control apparatus may be brought to bear on any part of such flam- mable liquids storage. 606.03 In buildings, rooms or other confined spaces in which flammable liquids are stored, combustible waste materials shall not be allowed to accumulate, except in closed metal containers. 607. First -aid Appliances: Where flammable liquids are - used or dis- pensed, first -aid fire -control equipment shall be provided in such quantities as public safety shall require. The number and type of appliances meeting the standards for "Fire Aid Fire Appliances"t adopted in 1950 by the National Fire Protection Association shall be deemed prima facie evidence of com- pliance with this section and three copies of this standard shall be filed with the city clerk by the Chief and kept available for examination.* This section should conform to local law and practice with respect to adoption by "reference" or where conformity with a published standard is deemed to be prima facie evidence of compliance with the ordinance. "National Fire Codes. Volume V (1951) ; also available from the National Board of Fire Underwriters (Pamphlet No. 70). iNational Fire Codes, Volume IV (1951) ; also available from the National Board of Fire Underwriters (Pamphlet 10). CHAPTER VII. PROCESSING PLANTS 29 CHAPTER VII. PROCESSING PLANTS. 701. Manner of Storage. 701.01 Class I or Class II flammable liquids shall be stored in closed containers, aboveground tanks outside buildings, or tanks underground or in enclosures as described in section 502.02. (See Chapter II of this ordinance.) 701.02 Class III flammable liquids shall be stored in containers, above- ground tanks outside buildings, or tanks underground or in enclosures as described in section 502.02. (See Chapter II of this ordinance.) 701.03 Storage in sealed cans, or similar portable closed containers not exceeding 5 gallons in individual capacity shall be permitted within buildings. Unlimited storage of flammable liquids in metal barrels and in drums not exceeding 60 gallons in individual capacity shall be permitted only in buildings or rooms used solely for such storage, and which meet the following design standards: Walls, floors and ceilings shall be of 8 in. of brick or concrete, or 4 in. of reinforced concrete. Openings to other rooms or buildings shall be provided with noncombustible liquid tight raised sills or ramps at least 6 inches in height and with fire -doors with heat -actuated releasing devices arranged to close doors automatically in case of fire. No combustible material shall be used in construction, except that floor surfacing may be of wood. Proper ventilation shall be provided. There shall be no opening to rooms below, except as made necessary by trade or manufacturing process. 701.04 Storage of flammable liquids shall be limited within buildings not meeting the requirements of Section 701.03, in accordance with the following subsections: 701.04-1 Within frame buildings, storage of Class I and Class II flammable liquids shall be prohibited; storage of Class III flammable liquids shall be limited to 60 gallons in any tank or container unless installed and constructed in accordance with Chapter II of this ordinance. 701.04-2 In other than frame buildings, Class I flammable liquids may be stored in closed containers or safety cans of not more than 5 gallon individual capacity and not exceeding a total of 25 gallons. Class II flammable liquids may be stored in closed containers or safety cans of not more than 5 gallons individual capacity, and in barrels, drums, or tanks of not more than 60 gallons individual capacity. The total quantity that may be stored in this manner shall be limited to 220 gallons. Class III flammable liquids may be stored in closed containers of not more than 5 gallons indi- vidual capacity, or in barrels, drums, or tanks not exceeding 120 gallons individual capacity. The total quantity stored in this manner shall be limited to 220 gallons. 702. Blending and Mixing. 702.01 Mixing or blending rooms or buildings shall meet the design standards of Section 701.03. Mixing or blending rooms or buildings shall be provided with natural or mechanical ventilation that will prevent the accu- mulation of flammable vapors in hazardous concentrations. Design of ven- tilating systems shall take into account the relatively high specific gravity of 30 FLAMMABLE LIQUIDS ORDINANCE the vapors. Openings in outside walls for natural ventilation shall be at floor level and shall be unobstructed except by louvers, or coarse screens. Mechan- ical systems for removing flammable vapors, designed, installed and operated in accordance with National Fire Protection Association Standards for the "Installation of Blower and Exhaust Systems," published in National Fire Codes, Vol. III, 1951* shall be deemed prima facie evidence of compliance with this section and three copies of this standard shall be filed with the city clerk by the Chief and kept available for examination.** 702.02 Vessels used for mixing or blending of Class I flammable liquids shall be provided with self -closing tight -fitting non-combustible lids that will control a fire within such vessel when applied thereto. Where such devices are impracticable, automatic or manually controlled chemical or other fire -extinguishing devices approved by the Chief shall be used. 702.03 Open flames and other sources of ignition shall not be used within the possible path of vapor travel where flammable liquids are mixed or blended in open containers. 702.04 Vessels shall be electrically connected by bond -wires, piping, or similar means, where differences of potential could otherwise be created by accumulation of static -electrical charges. 703. Dispensing from Containers Within Buildings. 703.01 Class I or Class II flammable liquids may be dispensed from approved safety cans, provided that there are no open flames or other sources of ignition within the possible path of vapor travel. 703.02 Class III flammable liquids may be dispensed from containers not exceeding 60 gallons in individual capacity by means of a pump or similar device taking suction through the top of the container. 704. Sources of Ignition: Open flames, heating devices and processes em- ploying temperatures capable of igniting the vapors of the flammable liquid used shall be prohibited in buildings, rooms and other confined spaces in which Class I or Class II flammable liquids are used in the open, or in which Class III flammable liquids are heated above their flash point in open con- tainers. Artificial lighting shall be by electricity only. Electrical devices located within the possible path of vapor travel shall be of a type approved for such locations. Electrical devices meeting the applicable standards of the "National Electrical Code" (1951) as published by the National Fire Pro- tection Association,* shall be deemed prima facie evidence of compliance with this section and three copies of this standard shall be filled with the city clerk by the Chief and kept available for examination.** *National Fire Codes, Volume III (1951) available from National Fire Protection Association, 60 Batterymarch St., Boston 10, Mass.; also available from the National Board of Fire Underwriters, 85 John St., New York 38, N. Y. (Pamphlet No. 91). •*This section should conform with local law and practice with respect to adoption by 'reference" or where conformity with a published standard is deemed to be prima facie evidence of compliance with this ordinance. {National Fire Codes, Vol. V (1951) : also available from the National Board of Fire Underwriters, 85 John St.. New York 38, N. Y. (Pamphlet No. 70). CHAPTER VIII. HEATING AND POWER 705. Housekeeping. 705.01 Wherever flammable liquids are stored in containers, provision shall be made and maintained for the detection of leakage. Leaking containers shall be immediately removed and the contents transferred to a tight container. 705.02 Access shall be provided by unobstructed aisles whereby first -aid fire -control apparatus may be brought to bear on any part of such flammable liquids storage. 705.03 In buildings, rooms or other confined spaces in which flammable liquids are stored, combustible waste materials shall not be allowed to accu- mulate, except in closed metal containers. 706. First -aid Fire Control: Where flammable liquids are stored, or are used in open vessels, or are dispensed within buildings or other enclosures, first -aid fire -control equipment shall be provided in such quantities as public safety shall require. The number and type of appliances meeting the Standards for "First Aid Fire Appliances"* adopted in 1950 by the National Fire Protection Association shall be deemed prima facie evidence of com- pliance with this section and three copies of this standard shall be filed with the city clerk by the chief and kept available for examination.** CHAPTER VIII, STORAGE AND USE OF FLAMMABLE LIQUIDS AS FUEL FOR HEATING AND POWER DEVICES. 801. Manner of Storage: All flammable liquids used for and connected to heating and power devices by means of piping shall be stored in accordance with Chapter 2 of this ordinance. 802. Oil Burners: Heating and other devices using oil burners shall be installed, maintained and operated in accordance with recognized safe practices. Burners and accessories such as piping, tanks, vents, control devices, etc., complying with the National Fire Protection Association Standards for the "Installation of Oil Burning Equipments" (1950),t. shall be deemed prima facie evidence of compliance with this section.** *National Fire Codes, Volume IV (1951) available from National Fire Protection Association, GO Batterymarch St_, Boston 10. Mass.; also published by the National Board of Fire Underwriters, 85 John St., New York 38, N. Y. (Pamphlet No. 10). **This section should conform with local law and practice with respect to adoption by "reference" or where conformity with a published standard is deemed prima facie evidence of compliance with the ordinance. tNational Fire Codes, Volume I (1948) ; also published by the National Board of Fire Underwriters (Pamphlet No. 31). 32 FLAMMABLE LIQUIDS ORDINANCE CHAPTER IX. REFINERIES AND OTHER PLANTS STORING AND HANDLING CRUDE PETROLEUM. 901. Location: No permit shall be issued for the construction of a refinery or plant storing or handling crude petroleum within that part of the city zoned solely for residential occupancies or for mercantile establishments predomi- nantly retail in character; or until approval has been given for the proposed location with respect to topography, nearness to places of public assembly, and adequacy of water supply for fire control. 902. Manner of Storage. 902.01 Crude petroleum shall be stored in tanks aboveground or under- ground. (See Chapter II of this ordinance.) 902.02 Other flammable liquids shall be stored in tanks aboveground or underground or in containers. (See Chapter II of this ordinance.) 903. Storage Tanks: Tanks for the storage of flammable liquids in tank farms and in locations other than process areas shall be located in accordance with Sections 202 —Location with Respect to Property Lines, and 203 — Spacing Between Tanks. 904. Unfired Pressure Vessels: Unfired pressure vessels shall be con- structed in accordance with recognized standards of design. Vessels meeting the standards of the API-ASME Code for "Unfired Pressure Vessels for Petroleum Liquids and Gases" (1950), or "Rules for Construction of Unfired Pressure Vessels, Section VIII, ASME Boiler Construction Code" (1949)* of the American Society of Mechanical Engineers, shall be deemed prima facie evidence of compliance with this section and three copies of this standard shall be filed by the Chief with the city clerk and kept available for examination!* 905. Location of Process Units: Process units shall be located so that they are accessible from at least one side for the purpose of fire control. Where topographical conditions are such that oil may flow from a processing area so as to constitute a fire hazard to property of others, provision shall be made to divert or impound the flow by curbs, drains, or other suitable means. 906. Fire Control: Water shall be available in pressure and quantity sufficient to provide cooling streams for any unit or any tank in the process- ing area. Hose and hydrants shall be available in sufficient number to provide application of cooling streams as required in this section. Fire. control chemicals and suitable application devices shall be available sufficient to extinguish a fire in any tank in the processing area, other than approved floating roof tanks. •Available from American Society of Mechanical Engineers, 29 West 39th St., New York, N. Y. **This section should conform with local law and practice with respect to adoption by "reference" or where conformity with a published standard is deemed to be prima facie evidence of compliance with this ordinance. CHAPTER X. - MODIFICATION, APPEALS, PENALTIES, ETC. 33 CHAPTER X. MODIFICATION, APPEALS, PENALTIES, ETC. 1001. Modification: The Chief shall have the power to grant exemption from application of the ordinance upon request in writing so to do when such request shows that the enforcement of the ordinance will cause un- necessary hardship to the petitioner, provided that said request shall not be granted where the requested use will constitute a distinct hazard to life or adjoining property. The particulars of such exemptions when granted shall be entered upon the permit issued. A copy thereof shall be retained by the chief. 1002. Appeals. 1002.01 An owner, lessee, agent, operator, or occupant aggrieved by any order issued pursuant to this ordinance, may file an appeal to the City Council within ten days from the service of such an order, and the City Council shall fix a time and place not less than five days nor. more than ten days thereafter when and where such appeal may be heard by it. Such appeal shall stay the execution of such order until it has been heard and reviewed, vacated or confirmed.* 1002.02 The City Council shall at such hearing, affirm, modify, revoke, or vacate such order. Unless revoked or vacated, such order shall then be complied with. 1002.03 Nothing herein contained shall be deemed to deny the right of any person, firm, corporation, co -partnership, or voluntary association to appeal from an order or decision of the City Council to a court of competent jurisdiction. Such appeal shall stay the execution of such order until it has been heard and reviewed, vacated or confirmed. 1003.. Penalties: Any person who shall fail to comply with the provisions of this ordinance or with an order of the Chief issued pursuant thereto and from which no appeal has been taken, or with such an order as affirmed or modified by the City Council or by a court of competent jurisdiction, within the time fixed therein, shall be fined not less than $................ or more than $................. The imposition of one penalty for the violation of such order shall not excuse the violation or permit it to continue. 1004. Repeal of Conflicting Ordinances: All former ordinances or parts thereof conflicting with the provisions of this ordinance are hereby repealed 1005. Severability: The City Council hereby declares that should any section, paragraph, sentence, or word of this ordinance be declared for any reason to be invalid, it is the intent of said City Council that it would have passed all other portions of this ordinance independent of the elimination Therefrom of any such portion as may be declared invalid. 1006. Effective Date: This ordinance shall take effect upon This section should conform to local law and practice with respect to terminology - and designation of agency to hear appeals. 34 FLAMMABLE LIQUIDS ORDINANCE APPENDIX A. Rooms, Cabinets and Outside Houses for the Storage of Flammable Liquids. These standards were developed by the Committee on Flammable Liquids in 1927 and 1928, and adopted by the Association in 1928. Minor editorial revisions have been made to bring this Appendix up to date in accordance with Committee action. Standards for the Construction of ROOMS, CABINETS AND OUTSIDE HOUSES FOR THE STORAGE OF FLAMMABLE LIQUIDS. 1. Flammable liquids, such as gasoline, lacquers, varnish, turpentine, paints, oils, etc., when stored in sealed original containers present a poten- tial rather than an active hazard. The latter results when the containers are open and when the liquids are transferred or handled by means of open containers or receptacles. This is due to the opportunity afforded the vapors to escape and become ignited by various means. The degree of hazard in such cases depends upon the capacity of the containers and to a certain extent upon the area of the liquid surface exposed. 2. When stored in original sealed containers (i. e., "dead storage"), the hazard is that due to the possibility of storage becoming involved by fire from without. Under such conditions the hazard, as in the case of open containers, will depend upon the character of the liquid as well as the capacity of the container. For this reason the storage of large amounts of flammable liquids in containers of large size, or handling or mixing opera- tions involving considerable amounts of such liquids should be segregated and restricted to specially constructed storage rooms or storage houses as hereinafter described. 3. Moderate quantities, should be stored in cabinets of construction in accordance with the specifications given herein. NOTE. Where drums constructed in accordance with the I. C. C. speci- fications are used as storage and handling containers, a storage room or cabinet may not be required, but this can only be determined by the Chief by consideration of the following features: character of liquid in question; capacity of individual containers and total quantity involved; type of building and nature of occupancy, and protection available. Withdrawal of liquids from drums in such cases shall be by pump only. 4. An inside storage room should be avoided; where one is necessary it should be located at or above grade, and where practicable in a comer of the building. Care should be taken to locate it away from sections having combustible and valuable contents. If situated over damageable materials or products, floors should be waterproofed, and provisions made for drainage to a safe place. APPENDIX A 35 GENERAL. (Applies wherever flammable liquids are stored or handled.) 5. All mixers, filters, pumps, motors, shafting, etc., shall be electri- cally grounded in an effective manner.. 6. Smoking shall be prohibited. TYPE A. INSIDE STORAGE OR MIXING ROOM. (For storage of large quantities or where there is extensive mixing and handling.) Nore. Figure I illustrates a typical Type A storage or mixing -room. 7. Construction. (a) Walls, floors, and ceilings shall be of 8 inches of brick or con- crete; 4 inches of reinforced concrete, or 8 inches of tile set in Portland cement mortar and plastered on both sides with Portland cement plaster to a thickness of 34 inch. (b) Exterior doors or doors opening to other rooms or building shall be provided with noncombustible sills or ramps raised at least 6 inches. (c) Floor shall be waterproof and arranged to drain to a safe loca- tion. (d) All door openings shall' be protected by a standard fire door of approved automatic or self -closing type, suitable for openings in fire walls. (e) Where other portions of the building or other properties are exposed, windows shall be protected in a standard manner. (f) Shelving shall be noncombustible. 8. Artificial lighting shall be by electricity with installation in ac- cordance with the National Electrical Code for hazardous locations. 9. Good natural ventilation is preferable in all storage and mixing rooms. Ducts should be of substantial metal construction extending above roof of building and terminating in an efficient suction creating device and having screened openings at floor level. Natural ventilation by other methods of equivalent efficiency may be provided. Where a mechanical ventilating system is necessary, installation shall be in compliance with the require- ments of Class B for the removal of flammable vapors as provided by the Standards for the Installation of Blower and Exhaust Systems.* 10. Heating shall be restricted to low pressure steam or hot water. 11. An approved waste can shall be provided for the storage of oily rags or waste; contents shall be removed daily. 12. For first aid fire protection there shall be provided extinguishing equipment of such type and amount as required by the Standards for First Aid Fire Appliances,** for Class B fires. Such rooms should also be protected by automatic sprinklers. ONational Fire Codes. Vol. III (1951). "National Fire Codes, Vol. IV (1951). 36 FLAMMABLE LIQUIDS ORDINANCE SECTION ei*nex pear l4 XVYVee wue! Peenrtreo Sm. !}!!l 3/.!n vRn WNW GUYv O�\ WITH nsl a xCase nalll ! vnite ene MCT4 RAY Y.W. a/3al1.C e. vent! ON lL!la�1e11 ❑ OIL nmYe NniGGPCOG CH IMT elope v.r.o PAILS can luIT. .0. CTe1c LKWI av rtCM exle!! Sit..MD Pose 101. 61 D. ND pmn N FIG. 1. Type A. Typical Storage and Mixing Room. APPENDIX A 37 TYPE B. INSIDE STORAGE OR MIXING ROOM. (The following specifications are intended to apply to inside storage and mixing rooms, where the quantities involved do not require Type A construction.) Non. Figure 2 illustrates a typical Type B storage or mixing room. !1D V[xTWiav Cs ntfwo I aesro eaurn U/1 o¢ eveaf rex•M TIN% vfMetHOD M xufil(en —T. ( Ifbx (.be rye 4 -MM VDn /1R Mate eyxe 3ECTI ON U. Cene,n Mamt C- rCTAt u'M. &Acx ♦IM C xCCP sTCC . 4At v ux ♦vx7 hme4M0 a aDrC {lpp9 Nix • win .'n..MAx !II ( • II CMpµ Doe1µ 1{ s S ii do t r M ^ L I 1 ]"MAtt¢P ajOOf <IMCIIT ♦WDR • (Zl6¢rWC.,N> ♦'%M swrCxa 4 I`(w+Ne♦ ieen 'VS. SO3POO¢ ♦e..M! e M tTL PLAN FIG. 2. Type B. Typical Storage and Mixing Room. 38 FLAMMABLE LIQUIDS ORDINANCE 13. Construction. (a) Walls shall be one of the following types of construction and shall be continuous from floor to ceiling and be securely anchored: Metal lath encased in solid cement plaster not less than 24 inches thick. Gypsum or cement plaster at least fl inch thick on metal lath on each side of stud partitions. Tile, gypsum or concrete block (cement plaster on each side to a thickness of % inch). In lieu of the foregoing any type of partition construction may be used which will afford one hour's protection against fire as determined by the American Society for Testing Materials specifications for standard fire test. (b) Ceiling shall be of construction equivalent to not less than 4 inch of cement or gypsum plaster on metal lath. (c) Floors if of wood should be protected with not less than 2 inches of concrete. If situated over damageable materials or products, floors should be waterproofed and provisions made for drainage to a safe place. (d) Door openings to other rooms or buildings shall be provided with noncombustible sills or ramps raised 6 inches. Such openings shall be pro- tected by standard Class C fire doors of approved automatic or self -closing type. (e) Where other portions of the building or other properties are exposed, windows shall be protected in a standard manner. (f) Shelving shall be non-combustible. 14. Artificial lighting shall be by electricity with installation in ac- cordance with the National Electrical Code for extra hazardous locations. 15. Good natural ventilation is preferable in all storage and mixing rooms. Ducts should be of substantial metal construction extending above roof of building and terminating, in an efficient suction creating device and having screened openings at floor level. Natural ventilation by other methods of equal efficiency may be provided. Where a mechanical ven- tilating system is necessary, installation shall be in compliance with the requirements of Class B for the removal of flammable vapors as provided by the Standards for the Installation of Blower and Exhaust Systems. 16. Heating shall be restricted to low pressure steam or hot water. 17. An approved waste can shall be provided for the storage of oily rags or waste; contents shall be removed daily. 18. For first aid fire protection there shall be provided extinguishing equipment of such type and amount as required by the Standards for First Aid Fire Appliances, for Class B fires. Such rooms should also be protected by automatic sprinklers. STORAGE CABINETS. 19 Storage cabinets may be used where it is desired to keep more than lb gallons of oils, varnishes, lacquers or similar materials inside buildings, no individual container to exceed 5 gallons capacity. Not over 50 gallons should be stored in any one cabinet. Such cabinets shall be of construction conforming with or equivalent in fire resistance to the fol- lowing requirements: Nora. Figure 3 illustrates a typical storage cabinet APPENDIX A 39 FLAMMAOLe •AEe+ON Dote KEEP I Te m waf 1155 TNN NPe.0Y4t FIRt AWAY nIT IVY I � i I 1 i f ELEVATION CA51NCT ID NAVt J AIM SPACt ON 5IDC3. TOP AND DOTTOr. DOOM 1 DC Orme Sni& CONSTRUCTION. PLAN NOTE : ALL JOINTS TO Ge TIGHT. no. s Typical Storage Cabinet. Joints shall be riveted, welded, or made tight by some equally efficient means. Doors shall be of construction equivalent to walls, provided with 3 -point lock and kept closed when not in use; door sill shall be raised at least 2 inches above bottom of cabinet. Cabinet shall be conspicuously labeled in red letters "FLAMMABLE, KEEP FIRE AWAY." Non. When deemed necessary, cabinets shall be vented. 40 FLAMMABLE LIQUIDS ORDINANCE 20. Bottom, top and sides of cabinet shall be made of sheet iron at least No. 18 gauge in thickness and double walled with 1% -inch air space. 21. Volatile flammable liquids shall be kept in metal safety cans, or other approved metal containers. OUTSIDE STORAGE HOUSES. 22. The type of construction to be employed for outside storage houses shall depend upon the proximity of proposed location to other buildings or structures. , 23.When an outside storage house is so located as to seriously ex- pose any nearby building or structure, construction should be equivalent in fire resistance to the Type A construction requirements for inside storage or mixing rooms. 24. When an outside storage house is so located as to moderately expose any other building or structure, construction should be equivalent in fire resistance to the Type B construction requirements for inside storage or mixing rooms. NOTE. In cases where exposures are slight or absent, the above re- quirement may be modified by the Chief. 25. The provisions of Types A and B construction for lighting, heat- ing, ventilating and first aid fire appliances shall be complied with. APPENDIX B. Recommended Safeguards and Safe Practices for the PROTECTION OF TANKS CONTAINING FLAMMABLE LIQUIDS IN LOCATIONS THAT MAY BE FLOODED. General. Pipe connections below allowable liquid level in tanks shall be provided with valves or cocks located as closely as practicable to tank shell. Such valves and their connections and fitting to the tank shall not be of cast iron. Section A. Above Ground Tanks. 1. Vertical Tanks. (a) No above ground vertical storage tank containing flammable liquids shall be so located that the maximum allowable liquid level within the tank is below the established maximum flood stage, unless the tank is provided with a guiding structure such as described in Section D. (b) Except at locations where there is an ample and dependable public water supply available at and below the established maximum flood stage, facilities independent of public water supply shall be provided for loading partially empty tanks with water. (c) In addition to the preceding requirements, each tank so located that more than 70 per cent, but less than 100 per cent, of its allowable liquid storage capacity will be submerged at the established maximum flood stage, shall be safeguarded by one of the following methods: APPENDIX 1. Tank shall be raised, or its height shall be increased, until its top extends above the maximum flood stage a distance equivalent to 30 per cent or more of its allowable liquid storage capacity, provided, however, that the submerged part of the tank shall not exceed 2% times the diameter; or, 2. As an alternative to the foregoing, adequate noncombustible struc- tural guides, designed to permit the tank to float vertically without loss of product, shall be provided. 2. Horizontal Tanks. (a) Except at locations where there is an ample and dependable public water supply available at and below the established maximum flood stage, facilities independent of public water supply shall be provided for loading partially empty tanks with water. (b) Each horizontal tank so located that more than 70 per cent of its storage capacity shall be submerged at the established maximum flood stage, shall be secured to a concrete or steel and concrete foundation of sufficient weight to produce adequate loading of tank when filled with flammable liquids. (c) Special provision shall be provided to equalize the internal and ex- ternal'pressures on the tank so as to prevent deformation of the tankand resultant expulsion of flammable liquid. One method of accomplishing this equalization of pressures is illustrated in Exhibit A. 3. Other Types of Tanks. Spherical and spheroidal tanks shall be protected by applicable methods as specified for either vertical or horizontal tanks. Section B. Underground Tanks. 1. Underground tanks containing flammable liquids at locations where there is an ample and dependable water supply available at and below the maximum flood stage and so installed that more than 70 per cent of storage capacity will be submerged at the maximum flood stage, shall be loaded with concrete or other approved loading material sufficient to prevent movement of the tank when filled with flammable liquid and submerged by flood waters. 2. At locations where there is no ample and dependable water supply, the tank shall be loaded with concrete as above required, and in addition, there shall be provided an emergency liquid supply which shall be sufficient to fill the tank during flood stages. 3. Where loading of underground tanks with liquids is impracticable because of the character of their contents or their use, each tank shall be safeguarded against movement when empty and when submerged by flood waters by loading with concrete or other approved solid loading material. Each such tank shall be so constructed and installed that it will safely resist external pressures due to flood waters. 4. In addition to the foregoing requirements the capacity of each new tank installed shall be restricted to not more than 3,000 gallons. When in- stalled but before backfilling, tank and fittings shall be tested for tightness at not less than 15 pounds per square inch. Greater test pressures may be required by the Chief when tanks are subject to submergence in excess of 30 feet. 42 FLAMMABLE LIQUIDS ORDINANCE w C C Y z 0 N Z C Z O CD tsj O Q N L d m o T'N E ` 3 T F C B rrj) aF (OH N y�_ w m e O i C Ali m C C a U7 N c o z C Y N Y � > V U $ E T OC Ii4 M — v mF > Ea ml Ls CI cn E 0 I�Z APPENDIX B 43 5. Where tanks are not designed to resist external pressure, special provision shall be provided to equalize the internal and external pressures on the tank so as to prevent deformation and resultant expulsion of flammable liquids. One method of accomplishing this equalization of pressures is illus- trated in Exhibit A. Section C. Independent Water Supply Facilities. 1. At locations where an independent water supply is required, it shall be entirely independent of public power and water supply. Independent source of water shall be available when flood waters reach a level not less than 10 feet below the bottom of the lowest tank on a property. 2. The self-contained power and pumping unit shall be so located or so designed that pumping into tanks may be carried on continuously throughout the rise in flood waters from a level 10 feet below the lowest tank to the level of the potential flood stage. 3. Capacity of the pumping unit shall be such that the rate of rise of water in all tanks shall be equivalent to the established potential average rate of rise of flood waters at any stage. 4. Each independent pumping unit shall be tested periodically to insure that it is in satisfactory operating condition. Section D. Structural Guides. 1. Structural guides for holding floating tanks above their foundations shall be so designed that there will be no resistance to the free rise of a tank, and shall be constructed of noncombustible material. 2. The strength of the structure shall be adequate to resist lateral move- ment of a tank subject to a horizontal force in any direction equivalent to not less than 25 pounds per square foot acting on the projected vertical cross- sectional area of the tank. 3. Where tanks are situated on exposed points or bends in a shore line where swift currents in flood waters will be present, the structures shall be designed to withstand a unit force of not less than 50 pounds per square foot. Section E. Safe Practices. 1. Water Loading. (a) The filling of a tank to be protected by water loading shall be started as soon as flood waters reach a dangerous flood stage. The rate of filling shall be at least equal to the rate of rise of the flood waters (or the established average potential rate of rise). (b) Sufficient fuel to operate the water pumps shall be available at all times to insure adequate power to fill all tankage with water. (c) All valves on connecting pipe lines shall be closed and locked in dosed position when water loading is completed. 2. Floating Tanks. (a) Where structural guides are provided for the protection of floating tanks, all rigid connections between tanks and pipe lines shall be disconnected 44 FLAMMABLE LIQUIDS ORDINANCE before the flood waters reach the bottom of the tank, unless control valves and their connections to the tank are of an approved type of extra heavy con- struction, designed to prevent breakage between valve and tank. (b) All valves attached to tanks other than those used in connection with water loading operations shall be closed and locked. (c)If a tank is equipped with a swing line, the swing pipe shall be raised to and secured at its highest position. Section F. Enforcement and Inspections. Because of its relation to the general problem of fire prevention and extinguishment in connection with the storage of flammable liquids, it is recommended that the enforcement of the foregoing requirements be placed with the fire department. The chief of the fire department or other enforcing official shall make periodic inspections of all plants where the storage of flammable liquids is such as to require compliance with the foregoing requirements, in order to assure the following: 1. That all flammable liquid storage tanks are in compliance with these requirements and so maintained. 2. That detailed printed instructions of what to do in flood emergencies are properly posted. 3. That station operators and other employees depended upon to carry out such instructions are thoroughly informed as to the location and operation of such valves and other equipment necessary to effect the intent of these requirements. APPENDIX C. RECOMMENDED PROCEDURE FOR THE ABANDONMENT OR REMOVAL OF SERVICE STATION UNDERGROUND TANKS. Flammable liquids not only require care in handling and use but proper attention should also be paid to abandoning tanks which have held flammable liquids. This is particularly true of underground service station tanks which are most frequently used for the storage of motor fuel and occasionally used for other flammable liquids such as crank case drainings (which may contain some gasoline). There have been some regrettable accidents where, through carelessness or curiosity, explosions have occurred because abandoned service station tanks had not been properly conditioned before being abandoned. The victims are usually children who cannot, of course, be expected to exercise judgment in such circumstances. In order to prevent future accidents from this cause, it is suggested that the safe procedures outlined below be followed in all cases where service station underground tanks are abandoned. Underground tanks taken out of service may be disposed of by any one of the three following means: (a) Being placed in "temporarily out of service" condition, (b) Abandoned in place, or, (c) Removed. APPENDIX C 45 In all cases where tanks are either rendered temporarily out of service or permanently abandoned, records should be kept of tank size, locations; date of abandonment, and method used for placing the abandoned tank in safe, condition. Safe procedures for carrying out each of the above methods of abandoning underground tanks are described below under their respective headings. In each case the numbered steps given shall be carried out successively. (a) Tanks Rendered "Temporarily Out of Service." 1. Remove all flammable liquid that can be pumped out with the service Pump. 2. The fill line, gauge hatch and pump suction shall be capped and secured against tampering. 3. The vent line shall be left open. NorE: As an alternate to the above procedure, the tank may be rendered gas free. (b) Abandoning Underground Tanks in Place. 1. Remove all flammable liquid from tank and from all connecting lines. 2. The suction. inlet, gauge and vent lines shall be disconnected. 3. The tank shall be flooded with water. 4. The tank and any remaining pipe stubs shall be filled with an inert, solid material. S. Cap or plug all connecting lines below ground level. (c) Removal of UndergroundTanks. 1. Remove all flammable liquid from tank and from connecting lines. 2. Disconnect the suction, inlet, gauge and vent lines. 3. The tank shall be flushed with water and rendered gas free as indicated by combustible gas indicator. 4. Cap or plug inlets and outlets and keep them capped or plugged during the transportation and storage of the tank. 5. If a tank is to be disposed of as junk, it should be re -tested for explosive vapors, and, if necessary, rendered gas free. After junking and before releasing to junk dealer, a sufficient number of holes or openings should be made in it to render it unfit for further use. 46 FLAMMABLE LIQUIDS ORDINANCE Standards Specified in Flammable Liquids Ordinance. Separate In NFPA NFPA Fire Codes NBFU Section Standard Pamphlet Volume Pamphlet Misc. 108 885 885 I 10418 I Book of ASTM Standards 1949 Part 5 202 11 11 IV 11 207 SOD I 20 207.01 207.04 207.04 801 - 404 91 91 405.02 101. 101 406.02 — API Standard No. 12A, 7th Edition, March 1941, "Specifi- cation for Standard Tanks with Riveted Shells for Oil Storage" API Standard No. 12c, 9th Edition, Oct. 1950, "Specifica- tion for Welded Oil Storage Tanks" API Standard No. 12B, 6th Edition. Sept. 1944, with Sup- plement No. 4 (Dec. 1949) "Specification for Standard Bolted Tanks" API Standard No. 12D, Srd Edition, Sept. 1944, "Welded Production Tanks" and "Sup- plement No. 2. (Aug. 1947)" thereto "American Standard Code for Pressure Piping (ASA) B 81.1. Edition of 1942. with Sup- plements B 81 -la, Nov. 1944 and B 81 -lb April, 1947) American Society of Much. Eng., 29 West 89th St.. New York 18, New York in 91 IN Circulars of the Association of American Railroads, No. 17-D, dated Aug. 1, 1947 and No. 17-E dated Aug. 1, 1947 (Asso- elation of American Railroads. 59 East Van Duren St.. Chi- cago, III.) STANDARDS SPECIFIED IN FLAMMABLE LIQUIDS ORDINANCE 47 Separate In NFPA NFPA Fire Coles NBFU Section Standard Pamphlet Volume Pamphlet Misc. 407 70 70 V 70 602.02 32 I 32 602.02 83 33 I 33 602.02 84 1 34 603.04 101 101 III - 604.02 91 91 III 91 606 70 70 V 70 607 10 IV 10 702.01 91 91 III 91 704 70 70 V 70 706 10 IV 10 802 81 I 31 904 API-ASME Code for "Unfired Pressure Vessels for Petroleum Liquids and Gases (1960)" or "Rules for Construction of Un- fired Pressure Vessels, Section VIII, ASME Boiler Construc- tion Code (1949) of the Amer- ican Society of Mechanical Engineers, 29 West 89th St.. New York 18, New York Related NFPA Standards. NFPA Number. 30-D Concrete Fuel Oil Tanks. 30-E Self Service Gasoline Sta- tions. 31 Oil Burning Equipment. 31-L Oil Burner Ordinance. 32 Dry Cleaning Plants. 325 Fire Hazard Properties of Flammable Liquid. 326 Warning Labels for Con- tainers of Flammable Liquids. 33 Spray Finishing Using Flammable Materials. 34 Dip Tanks. 35 Lacquer Manufacturing Plants. NFPA Number. 37 Internal Combustion En- gines. 385 Tank Vehicle for Flam- mable Liquids. 39-L Range Oil Burner Ordi- nance. 310 Small Heating and Cooking Appliances (Kerosene and Fuel Oil). 392 Gasoline Stoves. 393 Gasoline Blow Torches. 394-M Gasoline and Kerosene on the farm. 395 Farm Storage of Flam- mable Liquids. 304-L Petroleum Wharves. .. 305 Gasoline Fueling Stations for Small Craft. NATIONAL FIRE PROTECTION ASSOCIATION INTERNATIONAL Organization Member. Amatial Materials Am pine Prevention and Engineering National Metaiclad Dom Am Air Conditioning and Refrigerating Bureau of Texas National Paint, Varnish and Lamar Maehinery Am Fire Underwriters Inspection Bureau Am Air Filter Institute Florida Inspection and Rating Bureau National Safety Council Air Transport Am of America Gas Appliance Manufacturers Am National Task Truck Carriers. Ins. Alabama Inspection and Rating Bureau Georgia Inspection ad Rating Bureau National Wasp Air Hating and Au Awed LInes Am Gymnasium Seating Coma Conditioning Am American Rohm and Affiliated Ind"- Gypsum Am Nebraska Inspection Bureau trim Hawaii Fire Rating Bureau New Brunswick Board of Underwriters American Gas Am Heating. Piping and Air Conditioning New England Am of Fire Chiefs American Hospital Am Contractors National Am New England Fire Ins, Rating Am American Hotel Am Idaho Surveying and Rating Bureau New Hampshire Board of Underwriters American Institute of Architeea Illinois Inspection Bureau New York Board of Fire Underwriters Americo Institute of Electrical Re- Improved Risk Mutual New York Fire Insurance Rating gineer, Indian Bating Bureau Organization Americ.anInstitute of Steel Court. Inland Marine Underwriters Assn. Newfoundland Board of Fin IInder- Amerim Iron and Steel Institute Institute of Makers of Explains writers American Management Am Insulation Board Institute North Carolina Fire Insurance Rating American Marine Insurance Syndicates Insunuce Ann of Providence Bureau American Medical Am. resonance Rating Bureau of the Non Scala Board of Insurance Under - American National Red Corse District of Columbia writers Americas Petroleum Institute International Acetylene Am Oeuvre poor Is Seeurlte et 1'Orgaain- Amerim Society of Anesthesiologists International Ann of Electrical In- Don des Sectors American Transit Man speears Ohio Inspection Bureau American Warehousemen's Am International Ann of Fire Chiefs Oil -Heat Institute of America America Wood -Preservers' Am International Am of Fire Fighters Oil Insurance Aso Arkansas Inspection and Rating Bureau International Brotherhood of Electrical Oklahoma Inspection Bureau Asbestos Cement Product. Am Workers Oregon Insurance Rating Bureau Asphalt Roofing Industry Bureau International Municipal Sinai Am Oxychloride Cement Am Associated Reciprocal Exchange Iowa Inspection Bureau Pacific Coast Building OmeiaL' Cew- Am of American Railroads Kansas Inspection Bureau ferenee Am of Canadian Fire Marshals Kentucky Inspection Bureau Pacific Coast Inter -Mountain Am of Am of Casualty & Surety CO.. Lightning Rod Manufacturers Am Fire Chiefs Am of Edison Iliminatinwg CmpWa Liquefied Petroleum Gas Am Pacific Fire Rating Bureau Am of Iron & Stmt Enthusiasm Luutaians Rating and Fun Prevention Radio -Television Manufacturers Mn Am. of Mfrs. of Woodworking Ma- Bureau Red Cedar Shingle Bureau thine" Lumber Mutuals Royal Canadian Air Fora Am of Mill and Elevator Mutual Magnesim Am Safe Manufacturers National Am Insurance Companies Manufacturing Cbeslstt Am Rorie" of Motion Picture and Tai► Am of Mutual Fire W. ELdneen Maryland Fire Underwrite" Ridge vision Engineers Autmsfe Fire Alarm Am Bureau South Caroline Inspection and Rating Bond of Flee Underwriters of the Metal Lath Manufacturer. Am Bureau Pacific Michigan Inspection Buren South-Eeatea Underwriter? Am Board of Underwriters of New York Middle Department Am of fire IIn- Steel press Fabriatgn Am British Columbia Underwriters Am derwriten Steel Tank Institute Canadian Automatic Sprinkler Am Mississippi State Rang Bureau Tennessee Inspection Bureau Canadian Manufacturers' Am Missouri Inspection Bureau Terminal Elevator Grain Merchant? Canadian Underwriters' Am Motion Pia" Am of America Am Cast Iron Pipe Research An Mountain States Inspection Bureau Text. Board of Ins. Commissioners Central Station Fire Protection Am Mutual Fire Inspect. Bureau of N. E. Theatre Owners of America Central Traction and Lahting Bureau Chiago Board or Underwriters Mutual Fin Ion Am of N. E. Toy Pistol and Paper Cap Mnmaeta- Chlorine Mutual lass Research Bureau an Am clay PssedcG Am products National Am of Credit Men Transportation Ins. Rating Bureau CoGan Am National Am of Engine and Bat Underwriter' Laboratories county Bureau Cook Cam Manufacturers . Moral of (Spada Underwriters Sian Dentin Insurance ors Am National Am of Pen MmWagen Service Amories U. iertice dm Dominion Board of mamma Under- National Am of Agents S. Force U. S. Air writers Manufacturers National Am of Mutual e U. S. Department of Agr Dou Piro Prevention Am Ion. National Ann off uIna Army U. S. Department of the Army Douglasfir Plywood Am ssora National Am of Mutual Insurance U. S. Department of eeav Edlism Underwriters Am companies G. S. Department the Navy ketsInstitute Facto Electric Excuses National Automatic Sprinkler and Fin zof Vermiculite Institute Factory Mutual { Dlvlstm Control Am Washing Insurance Bureau Factory Insurance Am Asia National COW of Underwriter. en Surveying Washington Banmag and Bating facto, Mutual ue and National Blew Up and Paint Up Cam- Bureau Federation Mutual M Ins. Cam. on it Flown a ton Elects West Virginia Inspection Bureau Equip e t Manufacturer. Am. Fire Equipment e National Electrical Contractor? Am. m Western Actuarial Bureau Fin Insurance Boo Rating Benno National IAm Wewrin Canada Insurance Under - n fire Insurance Rating of N. I. National Elevator Mfg. Industry fg. stern O Am ee Fire Omen' Cmmittee Fire Prntee- National Lumber Manufacturer? Am actu Western Oil and Oat Am Mm Am National Machine Tool Boded Am Western Undenriten Am Over Thirteen Thousand Associate Members.