Ordinance: 6928
File Number: 2025-1991
AN ORDINANCE TO REQUIRE FIRE DEPARTMENT CONNECTIONS TO BE WITHIN 100 FEET OF A
FIRE HYDRANT BY AMENDING § 173.02 (C) AMENDMENTS, ADDITIONS, AND DELETIONS TO THE
FIRE PREVENTION CODE
WHEREAS, the Arkansas Fire Prevention Code previously required fire department connections to be within 100 feet
of a hydrant but, under the current code, fire department connection placement is left to the discretion of the fire code
official, requiring only that the connection be visible, immediately accessible, and approved; and
WHEREAS, to ensure consistency and operational efficiency, the Fire Marshal's Office has been requiring fire
department connections to be within 100 feet of a hydrant, in line with the existing standpipe requirement in NFPA
Standards; and
WHEREAS, the Fire Department recommends standardizing the requirement for fire department connection
placement, providing both design consistency and operational efficiency.
NOW, THEREFORE, BE IT ORDAINED BY THE CITY COUNCIL OF THE CITY OF FAYETTEVILLE,
ARKANSAS:
Section 1: That the City Council of the City of Fayetteville, Arkansas hereby amends § 173.02 (C) Amendments,
Additions, and Deletions to the Fire Prevention Code by re -numbering the subsection's existing language as follows:
"(C) Amendments, Additions, and Deletions to the Fire Prevention Code. The Fire Prevention Code shall be amended
as follows:
(1) Sprinklers. In addition to the requirements of the Fire Prevention Code and the Building Code, any new building
or alteration, addition or change of occupancy of existing buildings which exceeds three (3) stories including the
basement, or 50 feet or greater in height at the highest point of said building shall be protected by a complete
automatic sprinkler system designed and installed with compliance to applicable NFIPA Standards.
The following, as defined by Fire Prevention and Building Codes, shall be exempt from this provision:
(a) Airport Control Tower
(b) Open Parking Decks
(c) F-2 Occupancy"
Section 2: That the City Council of the City of Fayetteville, Arkansas hereby amends § 173.02 (C) Amendments,
Page 1
Ordinance: 6928
File Number. 2025-1991
Additions, and Deletions to the Fire Prevention Code by enacting the following new requirement:
"(2) 912.2.3 Proximity to Hydrant. Fire department connections for each sprinkler or standpipe system shall be located
not more than 100 feet from the nearest fire hydrant connected to an approved water supply, measured along the path of
vehicle travel unless otherwise approved by the fire code official."
PASSED and APPROVED on November 4, 2025
Approved:
Qt -�O�
Molly Rawn, Mayor
Attest:
Kara Paxton, City Clerk Treasurer
�� •G�'f Y O,r 'rG�%
;mc
=v� FAYETTEVILLE•�'O=
5
��9ti'4KANS
This publication was paid for by the City Clerk -Treasurer of the City of Fayetteville, Arkansas.
Amount Paid: $202.16
Page 2
CITY OF
JWM FAYETTEVILLE
ARKANSAS
MEETING OF NOVEMBER 4, 2025
TO: Mayor Rawn and City Council
THRU: Brad Hardin, Fire Chief
FROM: Granville Wynn, Financial Analyst - Fire
SUBJECT: Approval of an Ordinance for hydrant proximity
RECOMMENDATION:
CITY COUNCIL MEMO
2025-1991
Staff recommends adoption of the proposed ordinance requiring fire department connections (FDCs) for
sprinkler and standpipe systems to be located within 100 feet of the nearest fire hydrant connected to an
approved water supply, unless otherwise approved by the fire code official.
BACKGROUND:
The Arkansas Fire Prevention Code previously required FDCs to be within 100 feet of a hydrant. Under the
current code, FDC placement is left to the discretion of the fire code official, requiring only that the connection
be visible, immediately accessible, and approved. To ensure consistency and operational efficiency, the
Fayetteville Fire Marshal's Office has been requiring FDCs to be within 100 feet of a hydrant, in line with the
existing standpipe requirement in NFPA Standards.
DISCUSSION:
Establishing this ordinance will standardize FDC placement, providing both design consistency and operational
efficiency. Proximity to hydrants is critical for effective fire suppression. The Fayetteville Fire Department's
hose loads, appliances, and response model are built around a 100-foot standard, which allows firefighters to:
• Rapidly establish a reliable water supply,
• Supplement sprinkler and standpipe systems without delay, and
• Minimize the time from arrival to fire attack.
The proposed ordinance would codify this practice by adding Section 912.2.3, requiring FDCs to be located
within 100 feet of the nearest hydrant, measured along the path of vehicle travel, unless otherwise approved by
the fire code official. This requirement would apply to new construction and to occupancy changes requiring
sprinkler or standpipe installation.
BUDGET/STAFF IMPACT:
There is no budget impact related to this ordinance.
ATTACHMENTS: 3. Staff Review Form, 4. Proposed Ordinance Language Document —Hydrant Proximity
Mailing address:
113 W. Mountain Street www.fayetteville-ar.gov
Fayetteville, AR 72701
City of Fayetteville, Arkansas 113 West Mountain Street
Fayetteville, AR 72701
(479) 575-8323
Legislation Text
File #: 2025-1991
AN ORDINANCE TO REQUIRE FIRE DEPARTMENT CONNECTIONS TO BE WITHIN 100
FEET OF A FIRE HYDRANT BY AMENDING § 173.02 (C) AMENDMENTS, ADDITIONS,
AND DELETIONS TO THE FIRE PREVENTION CODE
WHEREAS, the Arkansas Fire Prevention Code previously required fire department connections to be
within 100 feet of a hydrant but, under the current code, fire department connection placement is left to
the discretion of the fire code official, requiring only that the connection be visible, immediately
accessible, and approved; and
WHEREAS, to ensure consistency and operational efficiency, the Fire Marshal's Office has been
requiring fire department connections to be within 100 feet of a hydrant, in line with the existing
standpipe requirement in NFPA Standards; and
WHEREAS, the Fire Department recommends standardizing the requirement for fire department
connection placement, providing both design consistency and operational efficiency.
NOW, THEREFORE, BE IT ORDAINED BY THE CITY COUNCIL OF THE CITY OF
FAYETTEVILLE, ARKANSAS:
Section 1: That the City Council of the City of Fayetteville, Arkansas hereby amends § 173.02
(C) Amendments, Additions, and Deletions to the Fire Prevention Code by re -numbering the
subsection's existing language as follows:
"(C) Amendments, Additions, and Deletions to the Fire Prevention Code. The Fire Prevention Code
shall be amended as follows:
(1) Sprinklers. In addition to the requirements of the Fire Prevention Code and the Building Code,
any new building or alteration, addition or change of occupancy of existing buildings which exceeds
three (3) stories including the basement, or 50 feet or greater in height at the highest point of said
building shall be protected by a complete automatic sprinkler system designed and installed with
compliance to applicable NFIPA Standards.
The following, as defined by Fire Prevention and Building Codes, shall be exempt from this
provision:
Page 1
Ordinance: 6928
File Number: 2025-1991
(a) Airport Control Tower
(b) Open Parking Decks
(c) F-2 Occupancy"
Section 2: That the City Council of the City of Fayetteville, Arkansas hereby amends § 173.02
(C) Amendments, Additions, and Deletions to the Fire Prevention Code by enacting the following
new requirement:
"(2) 912.2.3 Proximity to Hydrant. Fire department connections for each sprinkler or standpipe system
shall be located not more than 100 feet from the nearest fire hydrant connected to an approved water
supply, measured along the path of vehicle travel unless otherwise approved by the fire code official."
Page 2
Brad Hardin
Submitted By
City of Fayetteville Staff Review Form
2025-1991
Item ID
10/21/2025
City Council Meeting Date - Agenda Item Only
N/A for Non -Agenda Item
9/29/2025 FIRE (300)
Submitted Date Division / Department
Action Recommendation:
Staff recommends adoption of the proposed ordinance requiring fire department connections (FDCs) for sprinkler
and standpipe systems to be located within 100 feet of the nearest fire hydrant connected to an approved water
supply, unless otherwise approved by the fire code official.
N/A
Account Number
Project Number
Budgeted Item? No
Does item have a direct cost? No
Is a Budget Adjustment attached? No
Budget Impact:
Total Amended Budget
Expenses (Actual+Encum)
Available Budget
Item Cost
Budget Adjustment
Remaining Budget
N/A
Fund
Project Title
V20221130
Purchase Order Number: Previous Ordinance or Resolution #
Change Order Number:
Original Contract Number:
Comments:
Approval Date:
CITY OF
FAYETTEVILLE
ARKANSAS
Proposed language for hydrant proximity to fire department connections (FDC).
912.2.3 Proximity to hydrant. Fire department connections for each sprinkler or standpipe
stem shall be located not more than 100 feet (3048 mm) from the nearest fire hydrant
connected to an approved water supply, measured along the path of vehicle travel unless
otherwise approved by the fire code official.
Office of the Fire Marshal
303 W. Center St. www.fayetteville-ar.gov
Fayetteville, AR 72701
Form W .55
media
Account #: NWCL5004205
Company: CITY OF FAYETTEVILLE-CLERKS OFFI
113 W MOUNTAIN
FAYETTEVILLE, AR 72701
Ad number #: 553897
PO #:
Matter of: ORD 6928
AFFIDAVIT • STATE OFARKANSAS
ECEIVE
11/12/2025
CRY OF FAYETTEVILLE
CITY CLERKS OFFICE
I, Maria Hernandez -Lopez , do solemnly swear that I am the Legal Clerk of the NWA Democrat Gazette, a daily
newspaper printed and published in WASHINGTONBENTON county, State of ARKANSAS; that I was so related to
this publication at and during the publication of the annexed legal advertisement in the matter of
ORD 6928
Pending in the court, in said County, and at the dates of the several publications of said advertisement stated below, and
that during said periods and at said dates, said newspaper was printed and had a bona fide circulation in said County,
that said newspaper had been regularly printed and published in said county, and had a bona fide circulation therein for
the period of one month before the date of the first publication of said advertisement; and that said advertisement was
published in the regular daily issues of said newspaper as stated below.
And that there is due or has been paid the NWA Democrat Gazette for publication the sum of $202.16.
(Includes $0.00 Affidavit Charge).
NWA Democrat Gazette 11109125, NWA nwaonline.com 11109125
Legal Clerk
State ofARKANSAS, County of Sebastian ,
Subscribed and sworn to before me on this loth day of November, 2025
'T�2e:L�
N0 PUBLIC
O .•'��,22.203 'ro'•
�o `ol A R
Pig\-\G
N rco U o1 \'\��``��
Ordinance: 6928
File Number:2025-1991
AN ORDINANCE TO REQUIRE
FIRE DEPARTMENT CONNEC-
TIONS TO BE WITHIN 100 FEET
OF A FIRE HYDRANT BY AM END-
ING § 173.02 (C) AMENDMENTS,
ADDITIONS, AND DELETIONS TO
THE FIRE PREVENTION CODE
WHEREAS, the Arkansas Fire
Prevention Code previously re-
quired fire department connec-
tions to be within 100 feet of a
hydrant but, under the current
code, fire department connec-
tion placement is left to the dis-
cretion of the fire code official,
requiring only that the connec-
tion be visible, immediately ac-
cessible, and approved; and
WHEREAS, to ensure consis-
tency and operational efficiency,
the Fire Marshal's Office has
been requiring fire department
connections to be within 100
feet of a hydrant, in line with the
existing standpipe requirement
in NFPA Standards; and
WHEREAS, the Fire Depart-
ment recommends standardiz-
ing the requirement for fire
department connection place-
ment, providing both design
consistency and operational ef-
ficiency.
NOW, THEREFORE, BE IT OR-
DAINED BY THE CITY COUNCIL
OF THE CITY OF FAYETTEVILLE,
ARKANSAS:
Section 1: That the City
Council of the City of Fayet-
teville, Arkansas hereby amends
§ 173.02 (C) Amendments, Ad-
ditions, and Deletions to the Fire
Prevention Code by re -number-
ing the subsection's existing
language as follows:
"(C) Amendments, Additions,
and Deletions to the Fire Pre-
vention Code. The Fire Preven-
tion Code shall be amended as
follows:
(1) Sprinklers. In addition to
the requirements of the Fire
Prevention Code and the Build-
ing Code, any new building or
alteration, addition or change of
occupancy of existing buildings
which exceeds three (3) stories
including the basement, or 50
feet or greater in height at the
highest point of said building
shall be protected by a com-
plete automatic sprinkler sys-
tem designed and installed with
compliance to applicable NFIPA
Standards.
The following, as defined by
Fire Prevention and Building
Codes, shall be exempt from
this provision:
(a) Airport Control Tower
(b) Open Parking Decks
(c) F-2 Occupancy"
Section 2: That the City Coun-
cil of the City of Fayetteville,
Arkansas hereby amends §
173.02 (C) Amendments, Addi-
tions, and Deletions to the Fire
Prevention Code by enacting the
following new requirement:
"(2) 912.2.3 Proximity to Hy-
drant. Fire department connec-
tions for each sprinkler or
standpipe system shall be lo-
cated not more than 100 feet
from the nearest fire hydrant
connected to an approved water
supply, measured along the
path of vehicle travel unless
otherwise approved by the fire
code official."